Tile Fan Series – TFA203E
                                    
                                 
                                
                                
                                
                                    
                                    
                                    
                                    
                                    
                                    
                                        Performance Curve - TFA203E
                                        
                                     
                                    
                                 
                                
                                
                                
                                    
Description
                                    The Tile Fan Series was developed to simplify the installation of roof ventilators on tiled roofs. Designed to match the Boral and Monier concrete roof tiles, installation is a simple matter of lifting out a tile and putting the fan unit in its place.
                                
                                
                                
                                
                                
                                
                                
                                    
                                    
                                        Construction
                                        Cowls are moulded from UV stabilised plastic the bases are designed for tiled roofs. To install simply remove a tile and put the fan in its place. Steel components including fan and brackets have a corrosion resistant finish to suit arduous applications
                                     
                                    
                                    
                                        Motors
                                        Type - external rotor, squirrel cage induction motor.
Electricity supply - 220-240V, single-phase, 50Hz/60Hz.
Bearings - sealed-for-life, ball.
The TFA202 and 204 are speed-controllable.
                                     
                                    
                                    
                                        Internal Thermal Protection
                                        Auto-reset thermal contacts are supplied as standard.
                                     
                                    
                                    
                                        Testing
                                        Air flow tests to BS848:Part 1, 1980.
Noise data is based on tests conducted in accordance with BS848:Part 2, 1985
                                     
                                    
    Special Features
    
        Suitable for free and ducted intake installations. For ducted installations an inlet spigot is available as an optional extra.
Designed to match Boral and Monier concrete roof tiles.
Can be mounted at angles of 30°.
    
 
                                 
                                
                                
                                
                                    
                                    
                                        Suggested Specification
                                        The roof ventilators shall be of the Tile Fan Series as designed and manufactured by Fantech Pty. Ltd.
The axial impellers shall be direct driven by external rotor motors with integral thermal contacts.
All models shall be fully tested to BS848:Part 1, 1980 for air flow. Noise data is based on tests conducted to BS848, Part 2, 1985.
                                     
                                    
| Speed [rps] | Avg. dBA @ 3m | kWatts (Input) | Amps | Max.°C | Approx. Weight [kg] | 
| 43 | 44 | 0.06 | 0.3 | 50 | 4.6 | 
  
| Type | 63 | 125 | 250 | 500 | 1K | 2K | 4K | 8K | 
| Inlet | 60 | 67 | 66 | 64 | 59 | 46 | 49 |  | 
  
Dimensions
*All dimensions in mm, unless otherwise stated