Alpha Series – AE454D
Performance Curve - AE454D
Description
The Alpha & Beta Series of axial roof units are designed for a wide range of free intake and ducted exhaust air installations. These robust but lightweight exhaust units are available in
7 sizes in each range extending from 315 to 630mm diameter.
Features
Wide choice of speeds available.
All motors are speed-controllable.
Some 3-phase motors are 2-speed star/delta design.
Protective bird-mesh guards are fitted as standard on Alpha model unless fitted with optional shutters.
Shutters are fitted as standard to the Beta Series.
Robust, lightweight construction.
Can be used for free intake and ducted applications.
Can be mounted at angles up to 30°.
Supply air units can be supplied.Construction
Cowls are of UV-stabilised plastic or fibreglass.
Impeller blades are GRP as standard with an option of aluminium where required.
Metal components have a corrosion-resistant finish.
Shutters are fitted as standard to the beta series and are an optional extra on the Alpha series.
A bird-mesh guard is fitted on the Alpha model unless fitted with optional shutters.
Motors
Type - Squirrel cage induction motors
Electricity supply - 230V, single or 415V, 3-phase, 50Hz
Bearings- sealed-for-life, ball
Speed-controllable using electronic or auto-transformer controllers
Internal Thermal Protection
Manual-reset thermal protection is supplied as standard on all motors.
Testing
Air flow testing to BS848:Part 1, 1980
Noise tests to BS848:Part 2, 1985
Special Note
Refer to Fantech for fan selections at speeds other than shown.
When shutters are fitted ensure the roof unit is mounted with the shutter hinge pointing down the slope of the roof.
When shutters are fitted to the Alpha series derate performance by 15-20%.
Suggested Specification
The axial roof units shall be of the Alpha Series as designed and manufactured by Fantech Pty Ltd.
The axial impellers shall be of GRP (unless specified otherwise) and driven by speed-controllable motors with manual-reset thermal protection. The impellers run in pressed steel plates ensuring a certifiable performance.
The cowl shall be of the downflow discharge type and constructed from plastic and/or fibreglass. Steel components shall be corrosion protected.
All models shall be fully tested to BS848:Part1, 1980 for air flow and BS848:Part 2, 1985 for noise.Technical Data - AE454D
Speed [rps] | Avg. dBA @ 3m | kWatts (Input) | Amps | Max.°C | Approx. Weight [kg] |
---|
22 | 54 | 0.25 | 1.8 | 70 | 18 |
Sound Data
Type | 63 | 125 | 250 | 500 | 1K | 2K | 4K | 8K |
---|
Inlet | 74 | 75 | 72 | 71 | 70 | 67 | 64 | 56 |
Dimensions
*All dimensions in mm, unless otherwise stated
Wiring Diagram
Diagram shown is for single-speed only.
For 2-speed and special motors, contact Fantech for details.
Ancillaries