Description
The ECOtronic range of fixed pitch axial fans is available with infinitely variable speed control. This ultra energy efficient range can be designed into a Demand Control Ventilation (DCV) system that can include the Fantech Aviator controller and a range of sensors.
Features
Can be manually speed controlled by pressing 2 internal motor buttons
Can be remote speed controlled with either a 2-10V, 4-20mA, or 80-1600Hz input signal
Ultra energy efficient by combining aerofoil “Series 1” impeller blades and IE5* EC motors
Can be designed into a Demand Control Ventilation (DCV) system
Maximum operating speed can be adjusted from 1800rpm to 200rpm
Integrated electronics eliminate the need for external VSDs and current overload protection.
Can be factory pre-configured to suit specific applications and specific sensors
On board fault identification LED will flash according to fault type
Motor and junction box rated at IP55
Integrated “Fire Mode” function forces motor to continue working under adverse conditions
Available in 315, 355, 400, 450, 500, 560 and 630mm axial case sizes
Robust galvanised steel construction
Operating temperature: -20 oC to +60 oC when air velocity exceeds
5 m/s, otherwise -20 oC to +40 oC
Electrical supply: 230 - 277V single-phase, 50/60Hz input
Can be manually speed controlled by pressing 2 internal motor buttons
Can be remote speed controlled with either a 2-10V, 4-20mA, or 80-1600Hz input signal
Ultra energy efficient by combining aerofoil “Series 1” impeller blades and IE5* EC motors
Can be designed into a Demand Control Ventilation (DCV) system
Maximum operating speed can be adjusted from 1800rpm to 200rpm
Integrated electronics eliminate the need for external VSDs and current overload protection.
Can be factory pre-configured to suit specific applications and specific sensors
On board fault identification LED will flash according to fault type
Motor and junction box rated at IP55
Integrated “Fire Mode” function forces motor to continue working under adverse conditions
Available in 315, 355, 400, 450, 500, 560 and 630mm axial case sizes
Robust galvanised steel construction
Operating temperature: -20 oC to +60 oC when air velocity exceeds
5 m/s, otherwise -20 oC to +40 oC
Electrical supply: 230 - 277V single-phase, 50/60Hz input
Construction
Galvanised steel construction.
Testing
Air flow tests to ISO5801: 2007
Noise tests to BS848:Part 2, 1985
|
Technical Data - APEC063JP6WS011Speed [rps] | Avg. dBA @ 3m | kWatts (Input) | Amps | Max.°C | Approx. Weight [kg] |
---|
30 | 67 | 1.1 | 8.9 | 60 | 37 |
Sound DataType | 63 | 125 | 250 | 500 | 1K | 2K | 4K | 8K |
---|
Inlet | 79 | 78 | 82 | 82 | 81 | 81 | 78 | 76 | Outlet | 83 | 79 | 84 | 80 | 81 | 81 | 79 | 77 |
|