Seat Range – SEAT152S003
Location Designation
Project Notes
Seat Range
Description

Seat fans are designed to exhaust fumes from corrosive environments such as laboratories, fume cupboards, battery rooms and chemical plants. They include a high density, UV treated polypropylene housing and impeller to ensure maximum protection against acids and corrosion.

There are 5 models in the range to suit duct diameters from 125 to 315mm.

Features
  • Cowl rotates to 8 discharge positions by 45° increments
  • LG and RD handing from SEAT15-30, LG only for SEAT35
  • Air flows up to 2500L/s
  • Static Pressures up to 1500Pa
  • Forward curved centrifugal impeller
  • Direct drive, asynchronous motor, single or three phase, IP55
  • Explosion proof motors available on request
  • Recommended up to 60°C
  • Cowl rotates to 8 discharge positions by 45° increments
  • LG and RD handing from SEAT15-30, LG only for SEAT35
  • Air flows up to 2500L/s
  • Static Pressures up to 1500Pa
  • Forward curved centrifugal impeller
  • Direct drive, asynchronous motor, single or three phase, IP55
  • Explosion proof motors available on request
  • Recommended up to 60°C
Construction
High density, UV treated polypropylene housing and impeller that are resistance to chemical corrosion. Black epoxy coated metal stand.
Motor
Type - squirrel cage induction motor
Electricity supply – Motors to suit a wide range of voltages
and frequencies can be supplied
Bearings - sealed-for-life, ball
Can be fitted with speed-controller
Testing
Air flow tests to ISO5801:2017
Noise tests to ISO 13347

Technical Data - SEAT152S003

Speed [rps]Avg. dBA @ 3mkWatts (Input)Amps Max.°C Approx. Weight [kg]
48540.372.7408.1

Sound Data

Type631252505001K2K4K8K
Inlet7672747371625749
Outlet7574807871625951

 

Seat Range – SEAT152S003
Suggested Specification

The centrifugal extraction fans shall be of the SEAT Fan series as supplied by Fantech Pty. Ltd. and be of the model numbers shown on the schedule/drawing.

The housings and impellers shall be made from high density, UV treated polypropylene that is resistance to chemical corrosion. Impellers shall be forward-curved and the cowl preset to 1 of 8 discharge positions, rotated by 45° increments.

The centrifugal extraction fan shall be driven by a direct drive motor and designed to operate with a variable speed controller or variable speed drive.

They shall be fitted with inlet spigot and discharge flange, and come standard with an epoxy coated metal stand. Air flow test data shall be based on ISO5801:2017. Noise test data shall be based on ISO 13347.

 

Dimensions

ABCDEFGHJKLMN
17024020312510032307180360180340311

*All dimensions in mm, unless otherwise stated

Contacts



OFFICES & AGENTS

Victoria
Fantech Pty. Ltd.
Tel:+61 (03) 9554-7845

New South Wales
Fantech Pty. Ltd.
Tel:+61 (02) 8811-0400

Uniair Distributors Pty. Ltd.
Tel:+61 (02) 4961-6088
Refrigeration and Air Supplies
Tel:+61 (02) 4226-5133

South Australia
Fantech Pty. Ltd.
Tel:+61 (08) 8294-0530

Queensland
Fantech Pty. Ltd.
Tel:+61 (07) 3299-9888
Capricorn Air Conditioning
Tel:+61 (07) 4775-5222

Northern Territory
Fantech Pty. Ltd.
Tel:+61 (08 ) 8947-0447

Western Australia
Systemaire Pty. Ltd.
Tel:+61 (08) 9209-4999

Tasmania
Major Air Pty. Ltd.
Tel:+61 (03) 62736455

ACT
Idealair Group Pty. Ltd.
Tel:+61 (02) 6280-5511

Auckland
Fantech (NZ) Ltd.
Tel:+64 (09) 444-6266

Christchurch
Fantech (NZ) Ltd.
Tel:+64 (03) 379-8622

Wellington
Fantech (NZ) Ltd.
Tel:+64 (04) 566-0532