Twin Gamma Ultra Vertical – TGUE456
Location Designation
Project Notes
Twin Gamma Ultra Vertical
Description

The Twin Gamma Ultra Series of Mixed-Flow roof fans have been designed for use in commercial ducted exhaust applications. Incorporating twin vertical discharge fans, the unit provides 100% stand-by capacity.

These compact and low profile units are fitted with bird-mesh to prevent the entry of birds and vermin into the ducting or building.

They are available in 5 sizes, extending from 315 to 500mm diameter.

Features
  • Robust, lightweight construction.
  • Choice of speeds available.
  • Compact, low profile design.
  • Designed for vertical exhaust applications.
  • Backdraft-shutters are an optional extra (See special note).
  • Can be mounted at angle up to 30°.
  • Most 3-phase motors are 2-speed star/delta design

Note: Pressure loss across the shutter is now included in the performance curves.

  • Robust, lightweight construction.
  • Choice of speeds available.
  • Compact, low profile design.
  • Designed for vertical exhaust applications.
  • Backdraft-shutters are an optional extra (See special note).
  • Can be mounted at angle up to 30°.
  • Most 3-phase motors are 2-speed star/delta design

Note: Pressure loss across the shutter is now included in the performance curves.

Construction
Cowls are UV-stabilised plastic. Impellers are Mixed-Flow design and made from high performance injection moulded composite material. Steel components have a corrosion resistant finish. Bird-mesh guards are fitted as standard.
Motor

Type - external rotor, squirrel cage induction motor

Electricity supply - 230V, single and 415V, three-phase, 50Hz

Bearings - sealed-for-life, ball

Speed-controllable using electronic or auto-transformer controllers

All three-phase units are fitted with 2-speed star/delta design motors

Testing
Air flow tests based on ISO5801
Noise tests based on ISO13347-3

Technical Data - TGUE456

Speed [rps]Avg. dBA @ 3mkWatts (Input)Amps Max.°C Approx. Weight [kg]
15450.371.756078

Sound Data

Type631252505001K2K4K8K
Inlet6869686261595141
Outlet6171746767625342

 

Twin Gamma Ultra Vertical – TGUE456
Suggested Specification

The roof ventilators shall be of the Twin Gamma Ultra Series vertical exhaust type as designed and manufactured by Fantech Pty. Ltd. They shall provide dual fan vertical discharge to provide a 100% stand-by capacity and be of the model numbers shown on the schedule/drawing.

Impellers shall be made from high performance injection moulded composite material. They shall be Mixed-Flow design and driven by speed-controllable external rotor motors with integral thermal overload protection.

The windband shall be of the vertical exhaust design and formed from plastic. Steel components shall be corrosion protected.

All performance data shall be for a complete assembled unit based on ISO5801 for air flow and ISO13347-3 for noise.

 

Dimensions

ABCDEFGHJK
15806001680700189492875459966592

*All dimensions in mm, unless otherwise stated

Contacts



OFFICES & AGENTS

Victoria
Fantech Pty. Ltd.
Tel:+61 (03) 9554-7845

New South Wales
Fantech Pty. Ltd.
Tel:+61 (02) 8811-0400

Uniair Distributors Pty. Ltd.
Tel:+61 (02) 4961-6088
Refrigeration and Air Supplies
Tel:+61 (02) 4226-5133

South Australia
Fantech Pty. Ltd.
Tel:+61 (08) 8294-0530

Queensland
Fantech Pty. Ltd.
Tel:+61 (07) 3299-9888
Capricorn Air Conditioning
Tel:+61 (07) 4775-5222

Northern Territory
Fantech Pty. Ltd.
Tel:+61 (08 ) 8947-0447

Western Australia
Systemaire Pty. Ltd.
Tel:+61 (08) 9209-4999

Tasmania
Major Air Pty. Ltd.
Tel:+61 (03) 62736455

ACT
Idealair Group Pty. Ltd.
Tel:+61 (02) 6280-5511

Auckland
Fantech (NZ) Ltd.
Tel:+64 (09) 444-6266

Christchurch
Fantech (NZ) Ltd.
Tel:+64 (03) 379-8622

Wellington
Fantech (NZ) Ltd.
Tel:+64 (04) 566-0532