Description
The PowerLine Series® of In-Line Centrifugal Fans is designed for a wide range of duct mounted applications. They are most suitable in commercial and industrial applications where medium to high air pressure is required. They are available in various speed options and 8 sizes, extending from 315 to 710mm diameter.
Features
Robust, yet lightweight galvanised steel construction. Easy to fit 35mm TDF profile flange connections. Choice of external rotor or standard direct-drive TEFC motors. Large choice of speeds available. Most 3-phase external rotor motors fitted are 2-speed star/delta design. To improve energy efficiency, motors can be speed-controlled Motors complying with Ex d, Ex e, Ex nA and Ex tD Standards can be fitted. Can be mounted in any position. A range of matched ancillaries is also available.
Robust, yet lightweight galvanised steel construction. Easy to fit 35mm TDF profile flange connections. Choice of external rotor or standard direct-drive TEFC motors. Large choice of speeds available. Most 3-phase external rotor motors fitted are 2-speed star/delta design. To improve energy efficiency, motors can be speed-controlled Motors complying with Ex d, Ex e, Ex nA and Ex tD Standards can be fitted. Can be mounted in any position. A range of matched ancillaries is also available.
Construction
Galvanised steel housings with 35mm TDF profile flange connections.
Backward-curved centrifugal impellers. DD impellers are made from aluminium, ER impellers made from high performance injection moulded composite plastic.
Motor
Type - can be supplied with direct-driven external rotor or standard direct-drive TEFC motors.
Electricity supply - single or three-phase to suit a wide range of voltages and frequencies. Bearings - sealed-for-life, ball. External rotor motors are fully speed-controllable using electronic or auto-transformer controllers, however Sinusoidal filters are required when a variable speed drive is used. Standard direct-drive TEFC motors can be single or multi-speed and can be speed-controlled using a variable speed drive.
Testing
Air flow tests to ISO5801:2007
Noise tests to BS848:Part 2, 1985
|