Designing & Implementing Car Park System
Description
Estimating fan quantities
For the purpose of estimating costs, the steps on the following pages may be bypassed. Allow 5N of thrust per 100m2 of car park floor area to approximate the number of fans required.
The following steps are sufficient to create an initial ventilation system design.
A Computational Fluid Dynamics (CFD) analysis is often required to prove and further refine the design. Fans may need to be re-orientated, or in some cases, added or removed. A ventilation system can be tailored to suit virtually any car park. Before considering fan locations, the system layout will need to be identified. Refer to the previous section for information relating to system layouts and their suitability for particular car parks.
Step 1 - Assessing Car Park Geometry
First identify the supply and exhaust points in the car park. A system that complements the natural air path and is able to circulate or move air effectively within the car park should be chosen. Certain layout features may assist the effectiveness of a particular layout as shown below:
(a) ‘Natural air path’
- For ‘Linear Flow Systems’, supply and exhaust points should be spaced across the length of a car park.
- ‘Circular Mixing Systems’ are more tolerant of closely placed supply and exhaust points, but it is advisable to have a good amount of separation.
- Supply air points should include access ramps to outside.
- The ventilation system layout should complement the natural air path from supply to exhaust points.
(b) Ceiling features
To make the system more effective, position JetVent Fans in-line with supporting ceiling beams. If this is not possible, the system becomes less effective and more fans may be needed.
(c) Vertical clearance
Sufficient vertical clearance ensures maximum flexibility in system design. JetVent Fans may be recessed between ceiling beams to minimise the height of the system.
(d) Obstructions
If there is no option and the JetVent Fans must blow across ceiling beams, they have to be positioned a sufficient distance away from the obstruction. A horizontal distance eight times (8x) the height of the obstruction is generally sufficient. Nozzles on the JetVent units are specially designed and angled downwards for this purpose.
(e) Clashes with other services
Place mechanical service components, such as sprinklers, signs and pipework out of the JetVent’s discharge pattern area. Examples of these clashes are shown below.
Step 2 - Identify Fan Selection and Spacing
This table shows the maximum and recommended spacings between JetVent Fans for different
levels of fan thrust. These spacing distances are guidelines for fans placed in series. When using
these spacings, air velocities in most of the ventilated areas should be greater than 1m/s. AFCD
analysis will determine whether this is achieved in a particular car park design. In some ideal
cases, designs using the maximum distances have been effective.
Fan thrust depends on the operating speed of a particular fan unit and its thrust rating.
JetVent Selection
Step 1
Select the EC JetVent fan model based on their recommended spacing/ coverage and the space needing to be ventilated.
Step 2
Select Isolator and Smoke Detection Kit
ISOLATOR KIT
HP, USD, SD, LH JetVent Models
Code: JIU-ISOLATORKIT
SMOKE DETECTOR KIT
HP, USD, SD, LH JetVent Models Code: JIU-SMOKEKIT
ULH JetVent Model Code: JIU-SMOKEKIT-ULH
After a preliminary fan layout is completed using the spacing distances above, the layout may be checked for total installed thrust. Successful designs typically have approximately 5N of thrust per 100m2 of car park floor area. This thrust ratio also works well for estimating purposes.
Note that using higher rated JetVent fans generally makes the system more cost effective
than using more lower rated fans. This is due to the requirement of less JetVent fans and
hence saving on capital costs, installation costs and running costs. However, to effectively
ventilate car parks with low ceiling heights, unusual or irregularly geometries, selecting
more fans with smaller thrust ratings may be necessary.
Step 3 - Design Example
For the purpose of estimating costs, the steps below may be bypassed. Allow 5N of thrust per 100m2 of car park floor area to approximate the number of fans required.
Fans should be placed in the laneways with the air blowing along them. This is to avoid
obstructions such as parked cars and also ensure that the throw pattern of the selected fan is
long enough to reach the next JetVent fan.
An example of how fans are sized and placed based on floor area. [Download PDF]
JetVent Design parameters;
- Based on 5N per 100m2 floor area,
minimum total fan thrust = car park floor area x 5N/100m2
= 1920m2 x 5N/100m2
= 96N
- Minimum thrust criteria can be achieved with 4 x JIU-CPCEC-SD fans on preset speed (operating thrust 28.4N), total fan thrust = 28.4N x 4= 113.6N.
- Fans are spaced within the 35m spacing recommendation for thrust levels.
- Final fan to wall spacing under 40m maximum spacing guide lines for fan thrust. This is because the exhaust point is an area of low pressure, making it likely to enhance
the fan throw distance.
ComLink Design Parameters
Aviator controls should be placed in the Mechanical Services
Switchboard enclosure. The RS485 ComLink line must start at
the controller and then daisy chain to all the JetVent Fans and
Drives. The last connection must have an End-of-Line resistor.
If the line is greater than 1,000m or includes more than 32
connected devices, then a communications repeater must be
added to extend the line. A repeater can also be used where
the ComLink line branches off, such as at the beginning of
each level in a multi-story car park.
Fantech can provide support for electrical cabling mark-up
designs, to help ensure the most efficient ComLink strategy
is used.
Placement of CO sensors: Because the guidelines for positioning CO sensors in AS/NZS1668.2:2012 is based on a ducted system, we propose that the following guidelines be used as a starting point for their placement in a jet fan system.
- No part of the enclosure shall be greater than 25
metres from a sampling point. (A 50 metre
diameter circle around a CO sensor can show
coverage areas).
- Additional detectors shall be installed in areas
where people may congregate within the car park
and are not within separately ventilated areas.
- The most practical mounting position for a CO
sensor within a car park is the support columns.
- CO sensors will be more effective if placed in areas
where CO levels are likely to be high. Eg. Placing a
CO sensor in front of a fresh air intake is not
likely to be effective.
ComLink Design ParametersAviator controls should be placed in the Mechanical Services
Switchboard enclosure. The RS485 ComLink line must start at
the controller and then daisy chain to all the JetVent Fans and
Drives. The last connection must have an End-of-Line resistor.
If the line is greater than 1,000m or includes more than 32
connected devices, then a communications repeater must be
added to extend the line. A repeater can also be used where
the ComLink line branches off, such as at the beginning of
each level in a multi-story car park.
Fantech can provide support for electrical cabling mark-up
designs, to help ensure the most efficient ComLink strategy
is used.
Step 4 - Calculate Supply & Exhaust Rates
Section 4 of AS1668.2:2012 details requirements for ventilating car parks.
In particular, sub-sections 4.4.3 and 4.4.4 of the standard outlines calculations of exhaust
rates. In any of the two cases below, the exhaust air flow rate for a car park is taken as the
greatest of the following calculations:
Calculation of exhaust air flow rates (L/s)
Car parks with more than 40 spaces |
Car parks with less than or equal to 40 spaces |
a) 2000 x F x T (minimum air quantity for one operating car) |
a) 2000 |
b) 0.85 x P x (100 x n1+ n1 x d1 + n2 x d2 ) x E x T |
b) 2.5 x A |
c) 2.5 x A (minimum air quality based on area of car park) |
c) 400 n1 x P |
Supply air flows should range from 75% to 90% of the exhaust air quantity. This is based on the pressurisation of the car park, which should be 12Pa maximum.
Reference information for the calculation of exhaust air flow rates in the table above:
A = the area of the zone or level, in square metres
d1 = the average driving distance, in metres, within the zone or level under consideration for
the exit of a car parked there (see Clause 4.4.4.1)
d2 = the average driving distance, in metres, within the zone or level under consideration for
the exit of a car whose exit route passes through the zone or level under consideration,
but excluding any part of the exit route designated as queuing areas and ventilated in
accordance with Clause 4.6 (see Clause 4.4.4.1)
E = the staff exposure factor (E)
F = the staff usage factor (F)
n1 = the number of parking spaces in the zone of level under consideration (see Clause 4.3.2)
n2 = the number of parking spaces situated in other parts of the car park, having exit routes
passing through the zone or level under consideration
P = the parking usage factor (P)
T = the vehicle type factor (T)
If the car park has significant queuing areas for vehicles, refer to section
4.6 in AS1668.2:2012
|