Description
Seat fans are designed to exhaust fumes from corrosive
environments such as laboratories, fume cupboards, battery
rooms and chemical plants. They include a high density,
UV treated polypropylene housing and impeller to ensure
maximum protection against acids and corrosion.
Typical Application
Designed to exhaust fumes from corrosive environments such as laboratories, fume cupboards, battery rooms and chemical plants.
Features- Cowl rotates to 8 discharge positions by 45° increments
- LG handing
- Air flows up to 2500L/s
- Static Pressures up to 1500Pa
- Forward curved centrifugal impeller
- Direct drive, asynchronous motor, single or three phase, IP55
- Explosion proof motors available on request
- Recommended up to 60°C
Three Phase Models
Product Code | Avg. dB(A)@ 3m | kW | Amps | Max.Pre [Pa] | Max.Vol [m3/sec] |
---|
| 67 | 5.5 | 10.8 | 950 | 2.50 |
| 58 | 2.2 | 5.05 | 389 | 1.65 |