Table of Contents Table of Contents
Previous Page  102 / 416 Next Page
Information
Show Menu
Previous Page 102 / 416 Next Page
Page Background

MULTIFLOW SERIES

DUCT MOUNTED FANS

B

© FANTECH

2016

The Multiflow Series of In-Line Mixed-Flow Fans is designed for a

wide range of duct mounted applications. They are most suitable

in applications where higher air flows are required at medium

pressures. A particular feature of this product is its low noise

levels in comparison to axial and centrifugal selections.

They are available in various speed options and in 9 sizes,

extending from 250 to 800mm diameter.

Typical Applications

Commercial and industrial supply or exhaust air applications

such as shopping centres, office buildings, exhibition centres,

hotels, health centres, schools and universities.

Features

O

Robust, yet lightweight galvanised steel construction.

O

Easy to fit 35mm TDF profile flange connections.

O

Patented, adjustable pitch, mixed-flow impellers.

O

Large choice of speeds available.

O

To improve energy efficiency motors can be speed-controlled.

O

Motors complying with Ex d, Ex e, Ex nA and Ex tD.

Standards can be fitted.

O

Can be mounted in any position.

O

A range of matching ancillaries is also available.

Construction

Galvanised steel housings with 35mm TDF profile flange connections.

Patented, adjustable pitch, mixed-flow impellers made from

aluminium.

Sizes 250 to 450 are available in a choice of 2 impeller pitch

angle settings.

Sizes 500-800 are available in a choice of 4 or 5 impeller pitch

angle settings.

Motors

Type - standard TE motors.

Electricity supply - single or three-phase to suit a wide range of

voltages and frequencies.

Bearings - sealed-for-life, ball.

Motors can be single or multi-speed.

Three-phase motors for size 500 to 800, can be speed-controlled

using variable speed drives.

See pages

O-3/4

for details on standard TE motors.

If motors complying with Ex d, Ex e, Ex nA and Ex tD. Standards

are required, selections can be made from these pages.

Internal thermal Protection

Manual-reset protection is supplied as standard up to size 450.

For fans 500 and above, thermal protection is an optional extra.

Testing

Air flow tests to BS848:Part 1, 1980

Noise tests to BS848:Part 2, 1985

Wiring Diagram

See pages

N-6/7

, diagrams

DD1, 2, 3, 5, 6, 9

The Multiflow Mixed-Flow In-Line Fans shall be as designed and

manufactured by Fantech Pty Ltd and be of the model numbers

shown on the schedule/drawings.

The mixed-flow impeller shall be of patented, adjustable pitch

design, manufactured from aluminium and driven by standard

TE motors.

Housings shall be of galvanised steel with 35mm TDF profile

flange connections.

All models shall be fully tested to BS848:Part 1, 1980 for air flow

and BS848:Part 2, 1985 for noise.

Variable speed drives

Ref.

M-8-13

Vibration Isolators

Ref.

I-1

POW - Matching Flanges

Ref.

J-4

FT - Mounting Foot

Ref.

J-6

VA - Speed controllers

Ref.

M-5

SD - Star/Delta switch

Ref.

M-7

DESCRIPTION

ANCILLARY EQUIPMENT

SUGGESTED SPECIFICATION

HOW TO ORDER

B-42

* Please check with your local Fantech office if Ex d motors are available for

a specific selection.