TECHNICAL DATA
Model
CD..S
CE..S
Nom.
Speed
rev/sec
Low Air
Flow
High Air
Flow kW Amps* kW Amps*
314.
23
49 50
0.15 0.66
0.18 0.37
316.
** 15
45 42
0.07 0.54 0.09 0.15
354.
23
54 53
0.28 1.25
0.19 0.51
356.
15
47 45
0.07 0.32 0.13 0.22
404.
23
58 56
0.49 2.20
0.45 1.40
406.
15
49 48
0.17 0.80
0.23 0.73
408.
11
41 43
-
-
0.16 0.30
454.
23
61 59
0.76 3.50
0.77 1.47
456.
15
50 50
0.43 2.00
0.65 0.90
458.
11
44 46
-
-
0.15 0.35
504.
23
65 64
1.30 5.70
1.39 2.70
506.
15
52 52
0.53 2.50
0.65 1.20
508.
11
48 48
0.23 1.15 0.30 0.50
564.
23
69 69
-
-
2.16 4.10
566.
15
54 54
0.84 4.10
0.69 1.45
568.
11
49 50
0.32 1.50 0.39 0.79
634.
23
75 74
-
-
4.30 7.35
636.
15
61 58
-
-
1.10 2.20
638.
11
51 53
-
-
0.68 1.20
716.
15
63 60
-
-
2.20 4.30
718.
11
54 56
-
-
0.66 2.00
711.
9
48 50
-
-
0.28 1.20
CE.. 1 ph.
Avg. dB(A) @ 3
m
CD.. 3 ph.
Model
CD..S
CE..S
63 125 250 500 1k 2k 4k 8k
314.
Outlet
31 25 19 19 14 12 7 0
316.
Outlet
31 27 18 18 16 11 7 3
354.
Outlet
24 27 16 17 16 14 8 1
356.
Outlet
31 27 18 18 16 11 7 3
404.
Outlet
26 26 17 17 16 13 10 6
406.
Outlet
27 24 17 17 15 12 9 1
408.
Outlet
30 23 16 15 16 15 11 1
454.
Outlet
28 24 17 17 16 12 11 10
456.
Outlet
24 22 17 16 15 13 11 0
458.
Outlet
30 23 16 15 16 15 11 1
504.
Outlet
26 24 17 16 16 10 9 8
506.
Outlet
27 25 18 17 16 13 11 2
508.
Outlet
32 24 17 16 16 14 11 1
564.
Outlet
25 25 17 16 17 8 8 7
566.
Outlet
30 27 19 17 16 12 10 3
568.
Outlet
33 24 18 17 16 13 10 1
634.
Outlet
24 27 18 16 18 7 7 7
636.
Outlet
32 28 19 17 15 11 8 4
638.
Outlet
34 24 18 17 16 11 9 0
716.
Outlet
32 28 19 17 15 11 8 4
718.
Outlet
34 24 18 17 16 11 9 0
711.
Outlet
34 24 18 17 16 11 9 0
In-Duct Spectrum Corrections, dB*
* Add the In-Duct Spectrum Corrections to the closest dB(A) level shown on the
fan curve to obtain the In-Duct Sound Power Levels on the Discharge Side
of the Unit.
GAMMA SUPPLY SERIES