Table of Contents Table of Contents
Previous Page  272 / 416 Next Page
Information
Show Menu
Previous Page 272 / 416 Next Page
Page Background

H

© FANTECH

2016

Depth,

mm 300

600 750 900 1050 1200

200

300

400

Air Volume, L/sec

W-width, mm

450

90

135

180 270

200

135 180

270

360 450

340

225 270

400

540 630

475

315 360

540

720

The air flows tabulated are based upon a maximum pressure loss of 15 Pa.

CT - Cross-Talk

Model - S

1 - std. performance

2 - high performance

Width in cm

Depth in cm

- L

- U

- Z

C T

AIR PERFORMANCE DATA

CROSS-TALK ATTENUATORS

NOISE CONTROL PRODUCTS

HOW TO ORDER

The Q-Tech range of Cross-Talk attenuators has been

designed to provide low air flow resistance whilst maintaining

a high degree of acoustic attenuation.

The CT series should be considered wherever a relief air

passage is required to penetrate a room’s acoustic barrier.

Four styles are available in both standard and high

performance configurations:-

O

CTS

- for simple wall penetration above ceiling

O

CTL

- wall to ceiling penetration

O

CTU

- ceiling to ceiling penetration

O

CTZ

- installation within the wall

Installation - General

Special care should be taken when installing CT Series

Cross-Talk units to ensure maximum performance.

Consideration must be given to the sound rating of the wall

or ceiling being penetrated.

It is essential that a tight airseal is achieved between the

cross-talk unit and the wall/ceiling penetration.

When high performance units are used additional mass

lagging of the unit casing may be required to prevent flanking

transmission. This can usually be provided by building-in the

cross-talk unit during the building construction phase.

Performance

The Q-Tech CT Series acoustic performance is quoted as

airborne sound transmission loss as defined in AS1191:1985.

Performance data is based on Australian sourced

and manufactured products.

Selection Procedure

1. Select the Cross-Talk attenuator type that is required ie. CTS,

CTU etc.

2. Select high or standard performance attenuation as required.

3. When the relief air quantity is known, select from the

Air Performance Data table below, the width and depth

combination for your needs.

4. Determine final product code for ordering.

DESCRIPTION

HOW TO SELECT

H-18