RICKARD THERMO-DISC VAV DIFFUSER SERIES

K

K-2 RICKARD VAV DIFFUSERS

© FANTECH

2016

DESCRIPTION

The Rickard range of Thermo-Disc VAV ceiling diffusers help to

provide an indoor environment that maintains a consistent and

comfortable temperature. Diffusers only allow the required

volume of hot or cold air to enter the conditioned space

according to the diffuser’s set point. It is mechanically

controlled and thermally powered which means it is easy to

install and requires no external wiring or power supply.

Typical Applications

Can be used for single diffuser, single room applications through

to large open areas with multiple diffusers on multi levels. Ideal

as a retrofit solution in buildings that experience specific areas

that are either too hot or too cold.

Features

O

Reduces the energy consumption of a building by lowering

the demand on the air handling system.

O

Provides the occupant with control over their specific

environment. (Temperature set point adjustable from 19

o

C

to 24

o

C.

O

Each unit contains its own in-built temperature sensing and

volume control mechanism.

O

Lightweight, easy to install and ideal as a retrofit solution.

O

Available in 495* and 595mm square overall sizes and 150

to 300mm duct neck sizes.

O

Square to square and square to round diffuser styles

available.

O

Flush to the ceiling stylish look.

O

Maintains constant air movement from 100% down to 25%.

O

Discharge pattern ensures the air within the space is

thoroughly mixed.

O

Works when system is in cooling or heating mode.

Construction

Diffusers are of sheet steel construction and finished in a chip

resistant epoxy powder coating. Matt pen white is the standard

colour but others can be ordered to suit the architectural

requirements*. All internal components of non-metallic

construction are moulded in fire retardant Makrolon glass

reinforced plastic.

Mechanism

Air volume control is achieved through the vertical up and down

movement of the control disc within the diffuser. This increases

or decreases the aperture size which allows either more or less

conditioned air to enter the space.

The position of the control disc is varied by means of a wax

filled thermal element which responds to changes in sensed

room temperature. With a rise or fall in sensed temperature the

wax extends or retracts the plunger, causing the mechanism to

move the control disc to match the air volume requirements of

the space served by the diffuser.

Testing

Methods of testing the performance of air outlets and air inlets.

ANSI/ASHRAE Standard 70-2006 (RA 2011).

SUGGESTED SPECIFICATION

The diffusers shall be of the Rickard Thermo-Disc VAV ceiling

diffuser range as supplied by Fantech Pty Ltd and be of the

model number shown on the schedule/drawings.

They shall be manufactured from sheet steel and finished in

a chip resistant epoxy powder coating. All internal components

of non-metallic construction shall be moulded in fire retardant

Makrolon glass reinforced plastic.

Air volume control shall be achieved through the vertical up

and down movement of the control disc within the diffuser.

The position of the control disc is varied by means of a wax

filled thermal element which responds to changes in sensed

room temperature. It shall require no external wiring or power

supply.

Temperature set point shall be adjustable from 19°C to 24°C via

an adjustment ring located on the diffusers thermal mechanism.

All models shall be fully tested to ANSI/ASHRAE Standard

70-2006 (RA 2011)

* Minimum 12 weeks lead time.