© FANTECH
2016
Figure 5.2. - Isolation of roof mounted fans
Foam Tape
Rubber Grommet
Do not overtighten
to prevent distortion
Do not hard mount roof mounted fans to upstands.
Do isolate roof mounted fans from the duct work, and upstand
by using a foam tape between the top of the upstand and the
fan. Where the fan is fixed to the upstand with bolts or screws
use rubber / neoprene grommets.
Flexible
Connectors
5.0 VIBRATION ISOLATION
Figure 5.1. - Isolating vibrating fans
Vibration transmission through building structures is a frequent problem.
Flexible
Connectors
Do not bolt fan directly to the building structure as noise and
vibration can be transmitted directly to the building fabric.
Isolate fan and duct from the building structure with fan on
neoprene or spring isolators and suitable flexible connectors.
INSTALLATION DO’S AND DON’TS
INSTALLATION DO’S AND DON’TS