Table of Contents Table of Contents
Previous Page  54 / 416 Next Page
Information
Show Menu
Previous Page 54 / 416 Next Page
Page Background

WALL, WINDOW & CEILING MOUNTED FANS

A

A-32

© FANTECH

2016

FSU SERIES - AC SUPPLY

q

V

- Volume Flow, m /s

3

p

S

F - Fan Static Pressure, Pa

0.05

0.1

0.2

0.15

0.08

0.06

20

40

60

100

200

400

Free Field

= Avg. dB(A) @ 3m

FSU146

AC Motor

System

Lines

High Speed

Low Speed

Medium Speed

44

40

34

DESCRIPTION

The Filtered Supply Unit Series fan has been designed to

provide filtered outside air to a range of applications. Can be

wired in high, medium and low speed and includes a high

performance cross flow impeller.

Typical Applications

Supplies filtered air for applications from switchrooms

and dataroom pressurisation to libraries and classrooms.

Also suitable for areas that are typically serviced by

under-ceiling air conditioning units where a direct supply fresh

air intake is not possible or practical.

Features

O

Durable zinc coated steel housing, powder-coated

'off-white’.

O

Designed for in-wall mounting.

O

Strong and secure all steel construction.

O

Weatherproof, inlet grille is standard.

O

Powder-coated axial flow fan.

O

3-speed facility, connected on-site.

O

G4 filter included as standard, see Special Notes.

Construction

Zinc coated, 'off-white' powder-coated steel housing.

Integral all steel weatherproof inlet grille providing security.

Filter in fan discharge is standard.

Motors

Type - external rotor, squirrel cage induction motor.

Electricity supply- 230V, single-phase, 50Hz.

Bearings - sealed-for-life, ball.

Supplied with three speed facility, adjusted on site by a

wiring change or 3-speed switch - DSS1, refer to page

A-29

.

Class B motor, IP44 rated.

See pages

O-2/3

for details on these motors.

Internal thermal Protection

Auto-reset type fitted as standard.

Testing

Air flow tests to BS848:Part 1, 1980

Noise tests to BS848:Part 2, 1985

Performances shown are based on clean filters.

As air flow will be affected by room pressurisation, care should

be taken to ensure adequate air relief is provided.

Model

Number

Speed

Setting

Air

Flow

m

3

/sec

Avg.

dB(A)*

@ 3m Watts Amps

App.

Wt.

kg

FSU146-4-B1

1 (Hi)

0.20 44

205 0.95 30

2 (Med) 0.16 40

3 (Lo)

0.11 34

FSU.. 1 ph.

TECHNICAL DATA

* dB(A) figures shown are free field

Wiring Diagram

The unit is provided with a wiring strip mounted internally.

Active, Neutral and an Earth are required to be connected to the

strip. On-Off switches are by others.

Wiring access is provided to allow wiring from inside the

building. See page

N-9

, diagram

ER11

Special Notes

Filter

A 420 x 420mm washable filter is provided on the discharge

of the fan with a performance classification of G4 as tested

in accordance with AS1324.2-2001 and rated as per

AS1324.1-2001. These ratings are equivalent to the European

4/5 classification for filters as outlined in EN778. Access is

obtained by un-doing four dome nuts on the diffuser panel

and then turning four swivel clips.

Installation

This unit is designed to be installed flush to the inside wall,

except diffuser plate protrusion. Four mounting holes are

provided on the internal flange to secure the unit to the

inside wall, fasteners are by others. A flashing angle can

be provided for external use as an option. A penetration

size of 440 x 440mm is required.

SUGGESTED SPECIFICATION

The Filtered Supply Unit shall be of the FSU Series

fitted with an AC motor and supplied by Fantech

Pty Ltd. The units shall incorporate a cross

flow impeller and washable filter media in

an 'off-white' powder-coated galvanised steel

housing.Performance shall be based upon

tests conducted to BS848:Part 1, 1980

for air flow and BS848:Part 2, 1985 for noise.

DIMENSIONS

HOW TO ORDER

Quote the model number shown

in the technical data table.

Scan the QR Code

to view more

information online.

Dimensions in mm