TD-ECOWATT SERIES

DUCT MOUNTED FANS

B

© FANTECH

2016

Model

Number

TD-...

Type

dB(A)

@ 3m 63

125 250 500 1k

2k

4k

8k

250/100ECO

Inlet

39

53

48

55

58

55

52

43

37

250/100ECO

Outlet

38

55

48

56

59

52

51

42

36

250/100ECO

Breakout

34

50

45

55

51

50

49

37

30

350/125ECO

Inlet

37

54

44

53

55

53

51

43

36

350/125ECO

Outlet

38

55

46

54

58

53

51

42

35

350/125ECO

Breaktout

31

48

35

53

45

46

47

35

26

500/150ECO

Inlet

44

52

50

59

58

57

60

54

49

500/150ECO

Outlet

45

55

50

60

63

61

58

54

49

500/150ECO

Breakout

34

44

38

57

39

44

51

39

34

800/200ECO

Inlet

47

52

49

58

57

65

62

58

50

800/200ECO

Outlet

49

66

55

58

65

65

64

58

49

800/200ECO

Breakout

36

52

36

48

38

53

52

45

32

1300/250ECO

Inlet

64

65

63

77

77

82

79

71

64

1300/250ECO

Outlet

64

65

66

78

78

81

78

70

62

1300/250ECO

Breakout

62

66

67

79

77

79

75

66

57

2000/315ECO

Inlet

65

72

70

79

79

82

79

70

65

2000/315ECO

Outlet

66

72

71

81

80

83

80

71

65

2000/315ECO

Breakout

64

71

75

83

80

81

77

69

64

In-duct Sound Power Levels

L w dB re 1pW

NOISE DATA

Sound Levels are taken at medium-level pressure.

A B C D E FØ GØ

250/100ECO

100 60 156 80 303 97 176

350/125ECO

100 60 156 80 258 123 176

500/150ECO

111 60 173 80 295 147 200

800/200ECO

124 94 184 100 302 198 217

1300/250ECO

155 140 192 145 386 248 272

2000/315ECO

188 178 224 182 450 312 336

Model No.

TD-..

Dimensions, mm

FANS IN PARALLEL

DIMENSIONS

The TD-EcoWatt Fans can be installed in parallel by using the

same principle as the TD- Mixvent Fans. See

page B-16.

B-12

* Only required if other than standard single-stage unit.

HOW TO ORDER

Scan the QR Code

to view more