RICKARD VAV DIFFUSERS

RICKARD THERMO-DISC VAV DIFFUSER SERIES

© FANTECH

2016

DIMENSIONS

Neck/Spigot

size:

Ø150

Ø200

Ø250

Ø300

Square to Square style

Square to Round style

Neck/Spigot

size:

Ø150

Ø200

Ø250

Ø300

495

595

595

495

495

595

595

495

Neck/Spigot

size:

Ø150

Ø200

Ø250

Ø300

Neck/Spigot

size:

Ø150

Ø200

Ø250

Ø300

Neck

Size

(mm) Style

495mm x

495mm

595mm x

595mm

150

VSD1504S495 VSD1504S595

VCD1504S495 VCD1504S595

200

VSD2004S495

VSD2004S595

VCD2004S495

VCD2004S595

250

VSD2504S495 VSD2504S595

VCD2504S495

VCD2504S595

300

VSD3004S495

VSD3004S595

VCD3004S495

VCD3004S595

20 30 40

50

60

70

80

90

100

Air flow (L/s)

63 77 88 99 108 117 125 133 140

Throw (m)

2.0 2.1 2.7 3.0 3.3 3.5 3.7 4.0 4.2

NC Level (NC) -

-

-

-

26 28 31 33 35

Air flow (L/s)

96 118 137 153 169 184 195 207 218

Throw (m)

2.0 2.6 3.0 3.2 3.6 3.9 4.2 4.5 4.7

NC Level (NC) -

27 28 29 30 33 36 38 40

Air flow (L/s)

140 171 198 221 242 261 279 296 313

Throw (m)

2.4 2.6 3.2 3.5 3.9 4.2 4.5 4.7 5.1

NC Level (NC) -

27 29 31 33 36 38 40 42

Air flow (L/s)

176 216 250 280 307 332 355 377 398

Throw (m)

2.5 2.8 3.3 3.7 4.2 4.6 4.8 5.2 5.4

NC Level (NC) 27 28 30 32 35

37 39 41 43

RANGE

Model

Neck Total Pressure (Pa)

Dimensions in mm

Throw data is taken 25mm below the ceiling on a line through the centre of the diffuser with the control disc fully open & an air velocity of 0.25m/s.

Noise criteria levels apply to a single diffuser mounted in a room having a Sound Absorption of 10dB in octave bands having centre frequencies from

125Hz to 8000Hz (ie. the difference between Sound Pressure Level (dB re: 10-6 Pa) and Sound Pressure Level (dB re: 10-12 Pa) is equal to 10dB).

These levels represent only the noise generated by the diffuser and do not take into account any duct-borne noise.

Diffusers are factory set for a minimum of 30% of the maximum flow levels reflected above. It should be noted that minimum air flow settings are

approximate & may require to be reset on site to compensate for actual site system pressures.