MOTOR INFORMATION

© FANTECH

2016

REFERENCE INFORMATION

O-3

O

Re-starting the motors is achieved by two methods:-

O

auto-reset

O

manual-reset

The ‘auto-reset’ will permit the fan motor to automatically re-start when the windings

cool down. It is recommended they be connected to a current control relay.

The ‘manual-reset’ type requires the thermal contacts to be wired to a remote trip

contactor which has to be reset manually.

SUPPLY VOLTAGE

As the speed of external rotor motors can be controlled by varying the applied voltage,

they can be used where the voltage varies from the standard of 240V/1ph/50Hz or

415V/3ph/50Hz without detrimental effect to the motor. Indeed, on voltages as low as

200 volt on single-phase, or 346 volt on three-phase supply, only a slight reduction of

the motor speed would be detected.

TROPIC-PROOFING

Tropic-proofing consists of an anti-fungal treatment of the windings. Further

modifications may be necessary for high humidity applications.

WARRANTY

Note that warranty is void if the thermal contacts are not used.

AS/NZS3000:2007 wiring rules state that motors required to run unattended shall be

fitted with over-temperature devices such as thermal overload relays. If this is not

complied with warranty will be void.

A licensed electrical contractor or engineer, experienced in motor protection, should be

engaged to assess the motors and specific requirements of the installation.

STANDARD MOTORS

INTRODUCTION

Constructed to appropriate Australian, European and International Standards, standard

motors are used to drive a range of fans extending from window and wall units to large

industrial axial flow and centrifugal fans.

STANDARDS

The standard motors used are foot, flange or pad mounted, metric type and totally

enclosed as produced by most of the world’s major manufacturers. They will run

continuously with the minimum of attention and have been selected for their universal

interchangeability and availability in countries throughout the world. The motors comply

with the appropriate British, Australian and International Standards as far as:-

O

output

O

performance

O

dimensions

O

minimum energy performance standard (MEPS) to AS/NZS1359.5:2004

are concerned.

TEMPERATURE RANGE

AND ALTITUDE

In general the motors can operate in ambients from -20°C to +40°C at altitudes up to

1000 metres above sea level. Motors to operate outside this range can be supplied if

required.

ENCLOSURE STANDARD

The minimum is IP54 in accordance with the appropriate standards. IP55 enclosure can

be supplied for fully weatherproof applications.

FINISH

Standard finish is enamel paint top coat on suitable primer to give good appearance

and protection for general usage. Alternative finishes such as epoxy coating can also

be provided.