Table of Contents Table of Contents
Previous Page  70 / 416 Next Page
Information
Show Menu
Previous Page 70 / 416 Next Page
Page Background

TD-ECOWATT SERIES

DUCT MOUNTED FANS

B

© FANTECH

2016

RED - Reducer*

Ref.

B-17

RSK - Backdraft Dampers

Ref.

J-3

FGR - Filter Unit

Ref.

J-10

FC - Fast clamp

Ref.

J-5

MRJ - Inlet grille

Ref.

J-9

CC - Attenuators

Ref.

H-16

SJK - Backdraft Damper

Ref.

J-3

Model

Number

TD-..

Fan

Speed

rev/sec

Avg.

dB(A)

@ 3m Watts Amps

Max.

amb

°C

App.

wt.

kg

250/100ECO

40

39

20

0.17 60 2.0

350/125ECO

40

37

21

0.17 60 2.0

500/150ECO

43

44

50

0.35 60 2.7

800/200ECO

39

47

105

0.75 60 4.9

1300/250ECO

42

64

155

0.62 40 9.5

2000/315ECO

42

65

255

1.07 40 14.0

TD.. 1 ph.

ANCILLARY EQUIPMENT

TECHNICAL DATA

B-10

The TD-EcoWatt range of mixed-flow fans incorporates the latest

innovative EC motor technology.

Suitable for mounting in any position, the range is available to

suit standard duct sizes from 100 to 315mm diameter.

Typical Applications

Ideal for the ventilation of toilets, laundries, ensuites and kitchens

for homes, hotels and commercial premises.

Features

O

An energy efficient solution with state of the art

EC motor technology.

O

Speed-controllable from 10% to 100% via a 0-10V

analogue input signal.

O

High performance mixed-flow impeller.

O

Fans can be removed for maintenance or repair without

disturbing the duct system via specially designed support

brackets.

O

All models are designed for direct connection to standard

diameter circular ducting.

O

Integral mounting foot makes installation more simple.

O

Includes plug and lead for easy and quick installation.

O

Suitable for both supply and exhaust air applications.

Construction

Models 250/100 to 800/200 - casings manufactured from

reinforced, injection moulded, polypropylene plastic.

Impellers are made of injection moulded plastic and are

a mixed-flow design.

Models 1300/250 and 2000/315 - casings manufactured from

epoxy coated steel. Impellers are made of aluminium and of

mixed-flow design.

Motors

Type - high performance, energy efficient brushless DC motor.

Electricity supply - 90-260V, 50/60Hz for models 250/100 to 800/200.

- 230V, 50/60Hz for models 1300/250 and 2000/315.

Bearings - sealed for life, ball.

Motor protection IP44.

See pages

O-7

for details of these motors.

Internal Thermal Protection

Manual-reset thermal overload protection device in

accordance with mandatory requirements for in-line fans,

AS/NZS60335-2-80:2004

Testing

Air flow to ISO5801:Part 1 1997 or AMCA 210-99

Noise to ISO 13347-3 2004

Special Note

Avoid the use of spring-loaded backdraft dampers, extensive

lengths of duct and restrictive air valves with the 250/100ECO

and 350/125ECO models.

EC motors should be directly connected to their appropriate AC

supply. EC motors should not be regularly power cycled.

Multi-stage Fans

In addition to being used as single-stage fans, the TD-EcoWatt

can be arranged in parallel, in series or in both parallel and

series.

Such flexibility enables higher air flow and pressure demands

to be met. The principle of 2-stage parallel can be found on

page

B-16

; refer to the Fans by Fantech Product Selection

Program for details of other combinations.

* If it is necessary to connect the TD-2000/315ECO unit to 300mm diameter

ducting, it is recommended 2-RED031-030 reducers be used. In this situation

the performance will be reduced by approximately 7%.

SUGGESTED SPECIFICATION

The duct mounted fans shall be of the TD-EcoWatt Series as

supplied by Fantech Pty Ltd and be of the model numbers

shown on the schedule/drawings.

Impellers shall be of mixed-flow design and driven by a

speed-controllable, brushless EC-DC motor with manual-reset

thermal overload protection. Fans shall be capable of running

10 to 100% of capacity via a 0-10V analogue input signal.

It shall include an integral mounting foot, plug and lead and

specially designed support brackets to enable motor removal.

All fans shall be tested to ISO5801:Part1, 1997 and AMCA

210-99 for air flow and ISO 13347-3 2004 for noise.

DESCRIPTION