Table of Contents Table of Contents
Previous Page  157 / 416 Next Page
Information
Show Menu
Previous Page 157 / 416 Next Page
Page Background

© FANTECH

2016

D

ROOF MOUNTED FANS

D-11

Select the model required to handle the air quantity specified

from the performance graph.

Model

A

†

B C D E

†

App.

wt.

kg

App.

vol.

m

3

Min.

Free

Area

m

2

MRV1-BFC

210 260 30 200 346 1.0 0.02 0.017

MRV2-BFC

350 410 55 350 570 3.0 0.14 0.073

RV1-BFC

400 500 85 380 670 5.0 0.21 0.110

RV2-BFC

510 610 90 450 774 7.0 0.32 0.170

RV3-BFC

670 770 90 560 890 11.0 0.52 0.270

RV4-BFC

780 980 90 640 1180 16.0 1.10 0.410

Dimensions, mm

E

A

B (max.)

C

D

DIMENSIONS

HOW TO ORDER

DESCRIPTION

The robust Alpha Relief Vents with bushfire code compliance

have been designed to control relief air and the pressure within

buildings. They may also be used in a ducted system where the

fan is mounted remotely to the cowl. They comply with BAL-LOW

to BAL-40 of the Australian Standard AS3959:2009 Construction

of buildings in bushfire prone areas.

There are 6 models in the range capable of handling air flows

from 0.04 to 4.0m

3

/s.

Typical Applications

To control relief air and the pressure within buildings in bushfire

prone areas.

May also be used as the air intake and discharge point where

the fan is mounted remotely.

Features

O

Robust, heavy duty galvanised steel construction.

O

Fitted with high quality bronze mesh to provide protection

from burning embers.

O

All units are designed for curb mounting.

O

Can be mounted at angles up to 30°.

O

Can also be used as air intake units. Pressure losses are

approximately the same.

O

Compliant to AS3959:2009, upto and including BAL-40

Construction

Cowls are of galvanised steel.

Bronze mesh with a maximum of 2mm aperture fitted.

Special note

Construction of buildings in bushfire prone areas

AS3959:2009, clause 6.6.5(b) "Roof penetrations" states:

Openings in vented roof lights, roof ventilators or vent pipes

shall be fitted with ember guards made from a mesh

or perforated sheet with a maximum aperture of 2mm,

made of corrosion-resistant steel, bronze or aluminium.

SUGGESTED SPECIFICATION

The roof ventilators shall be of the Alpha Relief Air Vents Series

with bushfire code compliance as designed and manufactured

by Fantech Pty Ltd.

They shall be constructed from galvanised steel and include

ember protection mesh made from bronze or steel with

openings a maximum of 2mm.

They shall comply with BAL-LOW to BAL-40 of the Australian

Standard AS3959:2009 Construction of buildings in bushfire

prone areas.

ALPHA RELIEF AIR VENTS - BUSHFIRE CODE COMPLIANT

Scan the QR

code to view

more information

online.