Table of Contents Table of Contents
Previous Page  192 / 416 Next Page
Information
Show Menu
Previous Page 192 / 416 Next Page
Page Background

GL GAMMA SERIES - BUSHFIRE CODE COMPLIANT

ROOF MOUNTED FANS

D

© FANTECH

2016

D-46

Model

CD...VGL-BFC

CE...VGL-BFC A

†

B

†

C D E

†

Approx.

weight

kg.

Approx.

volume

m

3

314

310 410 50 310 520 16

0.10

316

354

400 500 50 420 670 26

0.22

356

404

400 500 50 420 670 26

0.22

406

408

454

620 720 60 525 900 49

0.50

456

458

504

620 720 60 525 900

57

0.50

506

51

508

564

620 720 60 525 900

65

0.50

566

56

568

634

710 810 60 665 1160

97

1.03

636

78

638

716

710 810 60 665 1160

95

1.03

718

83

711

E

C

D

A

B

Model

CD...VGL-BFC

CE...VGL-BFC

Nom.

Speed

r/s

LowAir

Flow

High Air

Flow kW Amps* kW Amps* 63 125 250 500 1k 2k 4k 8k

314.

23

Inlet 47

48

0.15 0.66

0.18 0.37

35 29 21 18 10 10 8 2

316.

15

Inlet 40

42

0.07 0.54 0.09 0.15 34 26 22 18 12 12 6 0

354.

23

Inlet 52

51

0.28 1.25

0.19 0.51

28 26 22 19 10 12 11 1

356.

15

Inlet 43

43

0.07 0.32 0.13 0.22 33 25 22 19 14 8 3 0

404.

23

Inlet 56

54

0.49 2.20

0.45 1.40

28 26 21 18 11 12 12 5

406.

15

Inlet 44

44

0.17 0.80

0.23 0.73

33 28 22 19 14 10 7 3

408.

11

Inlet 39

40

-

-

0.16 0.30 33 26 19 16 14 14 12 3

454.

23

Inlet 59

57

0.76 3.50

0.77 1.47

27 25 20 17 11 12 12 8

456.

15

Inlet 47

46

0.43 2.00

0.44 0.90

31 30 21 18 13 11 9 5

458.

11

Inlet 41

43

-

-

0.15 0.35 33 26 19 16 14 14 12 3

504.

23

Inlet 62

61

1.30 5.70

1.39 2.70

26 26 21 15 12 12 12 9

506.

15

Inlet 50

50

0.53 2.50

0.65 1.20

30 29 22 16 12 10 8 6

508.

11

Inlet 43

45

0.23 1.15 0.30 0.50 32 26 20 16 14 13 12 4

564.

23

Inlet 65

65

-

-

2.16 4.10

26 27 23 14 13 12 12 10

566.

15

Inlet 54

54

0.84 4.10

0.69 1.45

29 29 23 15 12 10 8 7

568.

11

Inlet 44

47

0.32 1.50 0.39 0.79 30 27 22 15 15 11 11 6

634.

23

Inlet 69

70

-

-

4.30 7.35

24 28 24 12 13 11 12 10

636.

15

Inlet 60

58

-

-

1.10 2.20

28 29 24 14 12 10 8 8

638.

11

Inlet 46

50

-

-

0.68 1.20 28 27 23 14 14 9 10 6

716.

15

Inlet 63

61

-

-

2.20 4.30

28 29 24 14 12 10 8 8

718.

11

Inlet 48

53

-

-

0.66 2.00

28 27 23 14 14 9 10 6

711.

9

Inlet 41

46

-

-

0.28 1.20 28 27 23 14 14 9 10 6

Electrical data in

bold

type refers to fans fitted with 2-speed star/delta motors as standard.

* Amperages shown are a guide only, refer to our Sales Department for accurate figures at time of order.

** Add the In-Duct Spectrum Corrections to the closest dB(A) level shown on the fan curve to obtain the In-Duct Sound Power Levels on the Inlet Side of the unit.

† The CE316VGL is not speed controllable.

CE.. 1 ph.

Avg dB(A) @ 3m

CD.. 3 ph.

Dimensions, mm

In-duct Spectrum Corrections, dB**

DIMENSIONS

TECHNICAL DATA & NOISE LEVELS