Table of Contents Table of Contents
Previous Page  240 / 416 Next Page
Information
Show Menu
Previous Page 240 / 416 Next Page
Page Background

JETVENT CAR PARK IMPULSE VENTILATION

© FANTECH

2016

JETVENT ANCILLARY EQUIPMENT

F-12

F

ECOVENT INTELLIGENT CONTROLLERS

Model

Number

JCC-..

Control

System

Protection

Class

Connectivity

Expansion

Module

Quantity

DIG1-SB

Digital

EC

IP40

Front panel

only

- Up to 24 JetVent

fans.

- Up to 48 pollutant

sensors.

- Up to 24 smoke

detectors.

0

ANA1-SB2

Analogue

IP40

Front panel

only

- Up to 16 JetVent

fans.

- Up to 2

pollutant sensors.

0

ANA1-SB6

Analogue

IP40

Front panel

only

- Up to 16 JetVent

fans.

- Up to 6 pollutant

sensors.

1

ANA1-SB10

Analogue

IP40

Front panel

only

- Up to 16 JetVent

fans.

- Up to 10 pollutant

sensors.

2

ANA1-SB14

Analogue

IP40

Front panel

only

- Up to16 JetVent

fans.

- Up to 14

pollutant sensors.

3

ANA1-SB18

Analogue

IP40

Front panel

only

- Up to 16 Jetvent

fans.

- Up to 18

pollutant sensors.

4

ANA1-SB22

Analogue

IP40

Front panel

only

- Up to 16 JetVent

fans.

- Up to 22

pollutant sensors.

5

TECHNICAL DATA

DIMENSIONS

105

60

110

Dimensions in mm

DESCRIPTION

The EcoVent Controller is a tailored solution, designed to

efficiently manage the ventilation equipment in enclosed

or semi-enclosed spaces that contain harmful vehicle

exhaust. It helps maintain good air quality when vehicle

traffic is high and conserve energy when it is low.

The EcoVent Controller works in conjunction with Fantech's

JetVent fans, CO and NO

2

pollutant sensors, integrated

smoke detectors, supply and exhaust fans, variable speed

drives and the BMS. It has been developed to help

increase the energy efficiency of a car park, while ensuring

the ventilation output is optimized. The EcoVent Controller

will vary the operating speed of the car park fans

according to the level of vehicle exhaust pollutants in the

environment.

The EcoVent Controller can be connected to the fire

system in the building to manage the automatic

starting/stopping of the fans when a fire is detected

(depending on fire/smoke management strategies), and

control the fans at the Fire Indicator Panel (FIP) by manual

speed control. Some applications also require links from

the BMS to monitor the operation of the JetVent system.

For car parks with ducted systems

The EcoVent Controller can also be installed with new

and existing ducted ventilation systems installed in

applications such as commercial and residential car

parks. It helps reduce energy usage by ensuring the

exhaust and supply fans only operate when needed

and at the speed required. The EcoVent Controller uses

CO and NO

2

pollutant sensors to read the level of

pollutant in the space and then relay this to variable

speed drives that modulate the fan speed.

Features

O

Digital EC model: Controls up to 24 JetVent Fans and

6 Vacon VSDs via MODbus.

Monitors up to 48 pollutant sensors

and 24 smoke detectors.

O

Analogue model: Controls up to 16 Jetvent fans

and Monitors up to 22 pollutant

sensors.

O

Factory pre-configured to suit specific car park

requirements.

O

Quick and easy to install and commission.

O

Proportional control of all fans according to pollutant

levels monitored.

O

BACnet connectivity for fire mode activation with

manual/automatic shut-off modes of operation.

O

Fresh air purge timer function.

O

Standalone or connects to a BMS via RS485,

BACnet IP, BACnet ms/tp and MODbus.