JETVENT CAR PARK IMPULSE VENTILATION
© FANTECH
2016
JETVENT ANCILLARY EQUIPMENT
F-12
F
ECOVENT INTELLIGENT CONTROLLERS
Model
Number
JCC-..
Control
System
Protection
Class
Connectivity
Expansion
Module
Quantity
DIG1-SB
Digital
EC
IP40
Front panel
only
- Up to 24 JetVent
fans.
- Up to 48 pollutant
sensors.
- Up to 24 smoke
detectors.
0
ANA1-SB2
Analogue
IP40
Front panel
only
- Up to 16 JetVent
fans.
- Up to 2
pollutant sensors.
0
ANA1-SB6
Analogue
IP40
Front panel
only
- Up to 16 JetVent
fans.
- Up to 6 pollutant
sensors.
1
ANA1-SB10
Analogue
IP40
Front panel
only
- Up to 16 JetVent
fans.
- Up to 10 pollutant
sensors.
2
ANA1-SB14
Analogue
IP40
Front panel
only
- Up to16 JetVent
fans.
- Up to 14
pollutant sensors.
3
ANA1-SB18
Analogue
IP40
Front panel
only
- Up to 16 Jetvent
fans.
- Up to 18
pollutant sensors.
4
ANA1-SB22
Analogue
IP40
Front panel
only
- Up to 16 JetVent
fans.
- Up to 22
pollutant sensors.
5
TECHNICAL DATA
DIMENSIONS
105
60
110
Dimensions in mm
DESCRIPTION
The EcoVent Controller is a tailored solution, designed to
efficiently manage the ventilation equipment in enclosed
or semi-enclosed spaces that contain harmful vehicle
exhaust. It helps maintain good air quality when vehicle
traffic is high and conserve energy when it is low.
The EcoVent Controller works in conjunction with Fantech's
JetVent fans, CO and NO
2
pollutant sensors, integrated
smoke detectors, supply and exhaust fans, variable speed
drives and the BMS. It has been developed to help
increase the energy efficiency of a car park, while ensuring
the ventilation output is optimized. The EcoVent Controller
will vary the operating speed of the car park fans
according to the level of vehicle exhaust pollutants in the
environment.
The EcoVent Controller can be connected to the fire
system in the building to manage the automatic
starting/stopping of the fans when a fire is detected
(depending on fire/smoke management strategies), and
control the fans at the Fire Indicator Panel (FIP) by manual
speed control. Some applications also require links from
the BMS to monitor the operation of the JetVent system.
For car parks with ducted systems
The EcoVent Controller can also be installed with new
and existing ducted ventilation systems installed in
applications such as commercial and residential car
parks. It helps reduce energy usage by ensuring the
exhaust and supply fans only operate when needed
and at the speed required. The EcoVent Controller uses
CO and NO
2
pollutant sensors to read the level of
pollutant in the space and then relay this to variable
speed drives that modulate the fan speed.
Features
O
Digital EC model: Controls up to 24 JetVent Fans and
6 Vacon VSDs via MODbus.
Monitors up to 48 pollutant sensors
and 24 smoke detectors.
O
Analogue model: Controls up to 16 Jetvent fans
and Monitors up to 22 pollutant
sensors.
O
Factory pre-configured to suit specific car park
requirements.
O
Quick and easy to install and commission.
O
Proportional control of all fans according to pollutant
levels monitored.
O
BACnet connectivity for fire mode activation with
manual/automatic shut-off modes of operation.
O
Fresh air purge timer function.
O
Standalone or connects to a BMS via RS485,
BACnet IP, BACnet ms/tp and MODbus.