© FANTECH
2016
F-13
F
JETVENT CAR PARK IMPULSE VENTILATION
POLLUTANT SENSORS
DESCRIPTION
The analogue pollutant sensor is available in carbon monoxide
(CO) and nitrogen dioxide (NO
2
) versions. They are ideal in
enclosed or semi-enclosed spaces that contain harmful vehicle
exhaust pollutants such as car parks, loading bays and drive
through "take away" facilities. It incorporates a corrosion
resistant, ABS/polycarbonate housing and hinged door that is
water and dust resistant.
Features
O
Linear 4 - 20 mA output signal.
O
RoHS compliant circuit boards.
O
Includes CEF (Calibration Extending Firmware) sensor.
O
CO/NO
2
simulation functions for commissioning.
O
Lower power draw means sensors can be powered
by EC motors.
TECHNICAL DATA
WIRING DIAGRAM
Model
Number
Detection
Type
Measuring
range
(PPM)
Protection
class
Dimensions
W x H x D
(mm)
LPT-TCO
CO
0-200
IP65
127 X 127 X 54
LPT-END
NO
2
0-10
IP65
127 X 127 X 54
24V DC
GND
4-20 mA Loop In
Control Panel
2-Wire Loop
Transmitter
24 V
24 V
SIG -
SIG +
BMS INTERFACE CARDS
DESCRIPTION
The EcoVent controller can be monitored by the 3 most popular
types of BMS systems: BACnet IP, BACnet ms/tp and MODbus.
If one of these technologies is being used simply select the
applicable interface card below.
SMOKE DETECTOR
COMMISSIONING KIT
DESCRIPTION
The commissioning kit will help check the activation of JetVent's
integrated smoke detector (featured on JIU-CPCEC models) by
using either the magnet or cold smoke included in each kit.
Important note
It is important to only test the smoke detectors with the cold
smoke aerosol can contained in this kit. Some other types of
artificial smoke may damage the smoke detector on the JetVent
JIU-CPCEC models.
Model Number
Kit includes
JIU-COMMISSION
- Magnet arm
- Cold smoke aerosol can
JETVENT ANCILLARY EQUIPMENT
Model
Number
Interface type
PCO1000WB0
BACnet IP
PCO1000BA0
BACnet ms/tp
PCOS004850
MODbus