Table of Contents Table of Contents
Previous Page  250 / 416 Next Page
Information
Show Menu
Previous Page 250 / 416 Next Page
Page Background

G

COOLING AND DE-STRATIFICATION FANS

© FANTECH

2016

G-4

JETVENT AIRMOVER SERIES

Model

Number

Speed

Setting

Discharge

Thrust

Avg.

dB(A)

@ 3m Volts kW Amps

App.

Wt.

kg

JVWD6

High 12N

54

415

0.69 1.45

85

Low 3N

50

0.39 0.79

JVWE6

-

12N

54 240 0.84 4.10

Distance from centre of fan in metres

6

8

1.5 -

3.0 m/sec

0.75 -

1.5 m/sec

0.5 -

0.75 m/sec

0.25 -

0.5 m/sec

10

12

Distance from fan in metres

14

16

18

20

0 1

1 2 3

2 3

Fan mounted 6m

above ground.

Measurements taken

1.5m above ground.

Ground Level

TECHNICAL DATA

VELOCITY PROFILE

DIMENSIONS

DESCRIPTION

The JetVent Airmover has been designed to provide air

movement in large enclosed areas such as warehouses

and recreation facilities.

Suspended from the ceiling, it provides a cross-flow of air to an

area that enhances heat transfer between the air and the human

body. This helps create a fresher environment that is more

comfortable to be in.

Typical Applications

Large indoor facilities where generating air movement is

essential to improving comfort. Examples of this are

warehouses, factories, workshops, gymnasiums and public

recreation facilities.

Features

O

Eliminates the build-up of hot, stagnant and polluted air.

O

Its gentle breeze creates less disturbance to the working

environment.

O

High level mounting position avoids plant operation

interference.

O

Adjustable discharge nozzle enables adjustment

of air flow direction.

O

High performance backward-curved centrifugal fan.

O

Available with single and three-phase motors.

O

Single-phase unit is speed-controllable and supplied

with 3-pin plug and lead. Three -phase unit can be

speed-controlled by using a Star/Delta 2-speed switch.

O

Long lasting galvanised steel construction with grey,

powder-coated finish.

O

For installations where unit is close to ceiling, model with

inlet on the underside face is available.

O

Other colours can be supplied.

Construction

Grey, powder-coated galvanised steel housing.

Adjustable discharge nozzle.

Backward-curved centrifugal impeller.

Motors

Type - external rotor, squirrel cage induction motor.

Electricity supply - 220-240V, single-phase, 50Hz; 415V,

three-phase, 50Hz.

Bearings - sealed-for-life, ball.

Single-phase motor - speed-controllable.

Three-phase motor - Can be wired in high or low speed.

2-speed available with installation of optional star/delta switch.

Isolator switch fitted to fan.

See pages

O-2/3

for details of these motors.

Internal thermal Protection

Internal thermal protection is supplied as standard on all units.

Wiring Diagram

Not required for single-phase fan.

For three-phase wiring see page

N-9,

diagram

ER9.

SUGGESTED SPECIFICATION

The ceiling suspended cooling fan shall be of the JetVent

Airmover Series as designed and manufactured by Fantech Pty

Ltd and be of the model numbers shown on the schedule/drawings.

Impellers shall be backward-curved design and driven by

speed-controllable external rotor motors.

It shall include an adjustable discharge nozzle and its housing be

manufactured from light grey, powder-coated, galvanised steel.

HOW TO ORDER

Scan the QR code

to view more

information online.

ANCILLARY EQUIPMENT

SD - Star/Delta switch

#

Ref. M-7

Dimensions in mm

# Applicable for JVWD6 unit (Three phase) only.

* Applicable for JVWE6 unit (Single phase) only.

VA - Speed controller*

Ref. M-5

Play Video