Table of Contents Table of Contents
Previous Page  28 / 416 Next Page
Information
Show Menu
Previous Page 28 / 416 Next Page
Page Background

WALL, WINDOW & CEILING MOUNTED FANS

A

A-6

© FANTECH

2016

The Vogue Series of modern ceiling/wall mounted fans is

suitable for commercial and light industrial applications

where powerful air flow and pressure performance are required.

Typical Applications

Suitable for a broad range of commercial and industrial exhaust

applications, ie. laundries, cellars and bars.

Features

O

Modern square plate, flush to the ceiling design.

O

Choice of speeds available.

O

Sturdy and robust construction.

O

Quick fitting swing locks retain the fan in place in

suspended ceilings or plasterboard walls and ceilings.

O

Holes incorporated for fixing to brick or concrete.

O

Grille can be easily removed for cleaning.

O

Can be used for ducted systems.

O

Can be mounted in any position.

O

Range of matched ancillaries are also available.

O

Models include plug and lead.

O

Reverse air flow can be provided (see Special Note)*.

Construction

The fan plate is of injection-moulded ABS plastic and the

impellers are of galvanised steel with a black powder coated

finish. The grille can be readily removed for cleaning. Access for

wiring is from the rear.

Motors

Type - external rotor, squirrel cage induction motor.

Electricity supply - single-phase 230V, 50Hz

Bearings - sealed-for-life, ball.

Speed-controllable.

Motor protection IP44.

See pages

O-2/3

for details on these motors.

If flameproof motors are required, refer to page

A-26/27

for full

selection information.

Internal Thermal Protection

Thermal contacts fitted as standard on all sizes.

Testing

Air flow tests to ISO5801:2004

Noise tests to BS848:Part 2 1985

*Special Note

Derate the air flow by at least 20% if the air flow direction

is reversed.

Not suitable for mounting above cook tops in kitchen

applications. Refer to Ring Plate Series, see page

A-8.

The fans shall be of the Vogue Series designed and

manufactured by Fantech Pty Ltd.

The axial impellers shall be direct-driven by speed-controllable

external rotor motors with integral thermal protection.

The square plates shall be of ABS plastic and the impellers from

powder coated, galvanised steel.

All models shall be fully tested to ISO5801:2004 for air flow and

BS848:Part 2, 1985 for noise.

VCW - Vogue

Fan diameter in cm

Fan speed, no. of poles

R - reverse flow if required

VCW

DESCRIPTION

SUGGESTED SPECIFICATION

HOW TO ORDER

VOGUE SERIES

Ducting, Louvres & Grilles

Ref.

L-6/14

VCW..DA - Duct

Adapter Ref.

A-7

WT - Wall tube

Ref.

J-11

VA - Speed controller

Ref.

M-5

VZ - Run-on timer

Ref.

M-14

Model

Number

VCW..

63 125 250 500 1k 2k 4k

202

78 69 68 66 69 65 60

204

60 70 54 56 54 49 40

254

63 64 57 57 57 54 47

302

63 66 74 75 80 75 71

304

60 64 64 61 64 62 55

306

53 57 55 53 54 52 44

In-duct Sound Power Levels

L

w

dB re 1pW

TECHNICAL DATA

* Amperages shown are a guide only. Refer to our Sales Department for accurate

figures at time of order.

Model

Number

VCW..

Free

Air

m

3

/s

Fan

Speed

rev/sec

Avg.

dB(A)

@ 3m Watts Amps*

Max.

°C

202

0.22 43

52

70 0.36 50

204

0.13 24

39

30 0.14 60

254

0.28 23

40

60 0.28 60

302

0.66 41

62

180 0.79 50

304

0.48 22

47

90 0.41 50

306

0.36 16

37

50 0.23 50

VCW.. 1 ph.

NOISE DATA

ANCILLARY EQUIPMENT