MOTOR INFORMATION

REFERENCE INFORMATION

© FANTECH

2016

O-6

O

MOTORS FOR HAZARDOUS AREAS (Cont.)

TEMPERATURE CLASSIFICATION

Hot surfaces can cause auto ignition of gases, vapours and dust, therefore it is

necessary to ensure that the maximum surface temperature of equipment introduced

into a hazardous area does not exceed the auto ignition temperature for the gas,

vapour or dust in the hazardous area.

Group I - Maximum Surface Temperature 150°C

Group II - are given a Temperature Class (T) based on the maximum surface

temperature of the equipment.

Temperature Classes are:-

T1 - 450°C

T4 - 135°C

T2 - 300°C

T5 - 100°C

T3 - 200°C

T6 - 85°C

ExtD motors will have a maximum permisseble surface temperature rating, but do not

follow the above temperature classes.

Note: For Ex d flameproof apparatus the external surface is the measured surface. For

other types of protection (e.g. Ex e) internal surfaces are of equal importance if the

explosive atmosphere has access to them.

FLAMEPROOF MOTORS

Ex d, FOR INDUSTRIAL USE

Three-phase motors

These motors are certified to Ex d and can fit a wide range of products as shown

throughout the catalogue. The certificate covers gas groups IIA and IIB, temperature

classification T4 and enclosure protection IP66.

The Standards complied with are IEC 60079-0:2004 and IEC 60079-1: 2007-04.

Single-phase motors

Fans with single-phase Ex d motors are featured on pages

A-26/27 & B-32/33

.

The certificate covers gas groups IIA, IIB and IIC, temperature classification T6 and

enclosure protection IP66.

The Standards complied with are IEC 60079-0:2004 and IEC 60079-1: 2007-04.

EXPLOSION PROOF MOTORS

Ex e, INCREASED SAFETY

Standard three-phase motors

These motors are certified to Ex e and can fit a wide range of products as shown

throughout the catalogue. The certificate covers gas groups IIA, IIB and IIC,

temperature classification T3 and enclosure protection IP55.

The Standards complied with are IEC 60079-0:2004 and IEC 60079-7:2006-07.

This Standard means the motors are also suitable for Ex n applications.

ELECTRICAL AND MECHANICAL

SPECIFICATION

Voltage:

Up to 500 Volts

Insulation:

Class ‘F’

Enclosure:

Totally enclosed, fan-cooled

Degree of Protection:

Up to IP66

Frequency:

50 or 60 Hz

LIMITING TEMPERATURE

The temperature of an external or internal surface to which the surrounding atmosphere

has access, shall not exceed the LIMITING TEMPERATURE specified.

RANGE

It is possible variations will arise in the kW/frame size/rpm, from one manufacturer to

another from that normally referred to in normal motor standards.