Products  Fans  By Mounting Type  Aeromix Destrat. Fans – ZFH160EC
Download Catalogue  Print Friendly Version

Aeromix Destrat. Fans – ZFH160EC

Aeromix Destrat. Fans

Description

Fantech’s Aeromix cooling and destratification fan has been developed to maximise air circulation and thermal comfort in large buildings with high ceilings. It incorporates an IE5* rated Electronically Commutated (EC) shaft motor delivering ultra energy efficient operation with the benefit of in-built variable speed control.

Fantech’s Aeromix cooling and destratification fan has been developed to maximise air circulation and thermal comfort in large buildings with high ceilings. It incorporates an IE5* rated Electronically Commutated (EC) shaft motor delivering ultra energy efficient operation with the benefit of in-built variable speed control.

Available in 400 and 500mm diameters, the Aeromix destratifies the space to create a more pleasant and productive working environment.

Features
  • Helps create a more productive, more comfortable environment that has the potential to reduce energy consumption
  • Used for spot cooling in summer and destratification in winter
  • Can be installed so its air flow avoids or targets specific areas
  • Adjustable air flow using a speed controller
  • Can be used as a demand-control destratification system with EC speed controller and two temperature sensors
  • Comes with 4 galvanised eyebolts that allow the fan to be suspended by cable
  • Alternatively, M10 threaded rod can be used to secured the Aeromix via 4 mount holes at the top of the fan
  • Finger guards on inlet side of the fan
Construction
Powder-coated aluminium case.
Axial flow aerofoil impellers are of high performance composite material.
Motors
Type - electronic commutated (EC) motor.
Electricity supply - 200-277V single-phase, 50/60Hz.
Bearings - sealed-for-life, ball.
IP55 rating.
Internal Thermal Protection
Motor overload protection is supplied as standard.
Testing
Air flow tests to ISO5801: 2007
Noise tests to BS848:Part 2, 1985
Special Note

EC motors should be directly connected to their appropriate AC supply. EC motors should not be regularly power cycled. If mounted less than 2.1 metres from floor level, additional finger guards must be fitted to outlet side of the fan (special order).
* The IE5 Efficiency level is not currently defined by the IEC Standard, however the intent is for IE5 motors to have approximately a 20% reduction in losses against IE4 motors.

Suggested Specification

The destratification fans shall be of the Aeromix Series as supplied by Fantech Pty Ltd and be of the model number shown on the schedule/drawings.

The axial impellers shall be made from high performance composite material. They shall be driven by an EC shaft motor with integrated speed controller and motor overload protection. Fan casings and motor plate shall be of aluminium with a powder coated light grey finish.

All models shall be fully tested to ISO5801:2007 for air flow and to BS848:Part 2, 1985 for noise.

 

Velocity Profile
Aeromix Destrat. Fans

Technical Data - ZFH160EC

Speed [rps]Avg. dBA @ 3mkWatts (Input)Amps Max.°C Approx. Weight [kg]
30621.18.96025

Dimensions

ABCD
500560584640

*All dimensions in mm, unless otherwise stated

Ancillaries