Tile Fan Series – TFA202E
Performance Curve - TFA202E
Description
The Tile Fan Series was developed to simplify the installation of roof ventilators on tiled roofs. Designed to match the Boral and Monier concrete roof tiles, installation is a simple matter of lifting out a tile and putting the fan unit in its place.
Construction
Cowl, base and inlet spigot are of UV-stabilised plastic.
Steel components have a corrosion-resistant finish.
Motors
Type - external rotor, squirrel cage induction motor.
Electricity supply - 220-240V, single-phase, 50Hz/60Hz.
Bearings - sealed-for-life, ball.
The TFA202 and 204 are speed-controllable.
Internal Thermal Protection
Auto-reset thermal contacts are supplied as standard.
Testing
Air flow tests to BS848:Part 1, 1980.
Noise data is based on tests conducted in accordance with BS848:Part 2, 1985.
Special Features
Suitable for free and ducted intake installations. For ducted installations an inlet spigot is available as an optional extra.
Designed to match Boral and Monier concrete roof tiles.
Can be mounted at angles of 30°.
Suggested Specification
The roof ventilators shall be of the Tile Fan Series as designed and manufactured by Fantech Pty. Ltd.
The axial impellers shall be direct driven by external rotor motors with integral thermal contacts.
All models shall be fully tested to BS848:Part 1, 1980 for air flow. Noise data is based on tests conducted to BS848, Part 2, 1985.
Technical Data - TFA202E
Speed [rps] | Avg. dBA @ 3m | kWatts (Input) | Amps | Max.°C | Approx. Weight [kg] |
---|
43 | 52 | 0.08 | 0.37 | 70 | 4.6 |
Sound Data
Type | 63 | 125 | 250 | 500 | 1K | 2K | 4K | 8K |
---|
Inlet | 67 | 69 | 73 | 71 | 66 | 65 | 59 | |
Dimensions
*All dimensions in mm, unless otherwise stated
Wiring Diagram
Diagram shown is for single-speed only.
For 2-speed and special motors, contact Fantech for details.
Ancillaries