Products  Fans  By Application  HC Series - High Capacity Axial Roof Fans
Download Catalogue  

HC Series - High Capacity Axial Roof Fans

HC Series - High Capacity Axial Roof Fans

Description

The High Capacity (HC) and Smoke-Spill (SS) Series of vertical exhaust axial roof ventilators have been designed for use in commercial and industrial applications. They are built to handle clean air, toxic, noxious and explosive gases as well as handling air at elevated temperatures. There are 10 sizes in the series extending from 500 to 1800mm diameter.
Typical Application
The HC model exhausts air from a wide range of commercial and industrial installations, ranging from clean air through to toxic, noxious and explosive gases. The SS model is designed for high temperature air exhaust applications.
Features
  • Robust and durable galvanised steel construction.
  • Adjustable pitch impellers can provide a wide range of performances.
  • Available in a range of speeds to suit specific applications.
  • Can be used for free air intake and ducted applications.
  • Impellers can be GRP, aluminium, nylon or anti-static (max 1400mm dia) to suit specific applications.
  • Designed to handle clean air, toxic, noxious and explosive gases as well as handling air at elevated temperatures such as for smoke-spill applications.
  • All non-hazardous motors are speed-controllable using variable speed drives.
  • Multi-speed motors, as well as motors to meet Ex d, Ex e, Ex nA and Ex tD Standards can be supplied.
  • Construction
    Galvanised steel cowl. Shutters are fitted as standard. Impeller blades can be GRP (standard), aluminium, nylon or anti-static to suit the application.

    Motors
    Type - squirrel cage induction motors
    Electricity supply - 415V, 3-phase, 50Hz
    Bearings - Sealed-for-life, ball
    All standard motors in HC range can be speed-controlled using variable speed drives.
    Motors with 2-speed windings, or to meet Ex d, Ex e, Ex nA, Ex tD or smoke-spill applications can be supplied.

    Internal Thermal Protection
    Thermistors can be fitted on request. If fitted on Smoke Spill Series they must not operate under smoke-spill mode.

    Testing
    Air flow testing - 500-1000mm diameter - BS848:Part 1, 1980
    1250-1800mm diameter - ISO5801:1997
    Noise testing to BS848:Part 2, 1985

    Smoke-spill Application
    The SS Series of smoke-spill fans has been fully tested to meet the air performance and high temperature requirements of Standards AS/NZS1668.1:1998 and AS4429:1999.

    Discharge damper fail-open latching
    An additional requirement of AS/NZS1668.1:1998 with respect to un-sprinklered buildings (300C for 30mins) requires dampers to fail-open during smoke spill operation.
    The fail-open discharge damper latches come in two forms; the first being a manual release type requiring manual closing after the fan has been run. The second design, an electro-mechanical type permits the shutter latch to release and close automatically after the fan stops.
    For advice on smoke-spill wiring requirements refer to AS/NZS1668.1:1998.