ROOF MOUNTED FANS

D-7

DESCRIPTION

Model

RDLE..

RVLE..

RSSL..

Fan

Speed

rev/sec

Max.

Motor

kW

App. vol.

RD..

m

3

App. vol.

RV..

m

3

0504

24

1.5

0.83

0.72

0506

16

0.37

0564

24

2.2

0.83

0.72

0566

16

0.75

0634

24

4

1.60

1.30

0636

16

1.1

0638

12

0.55

0714

24

5.5

1.60

1.40

0716

16

2.2

0718

12

0.75

0804

24

7.5

3.10

1.80

0806

16

4

0808

12

1.5

1004#

24

7.5

3.80

2.60

1006

16

5.5

1008

12

3

ALPHA & BETA INDUSTRIAL SERIES

The Alpha & Beta Industrial Series of axial roof units are

designed for a wide range of free intake and ducted exhaust

systems. These durable and robust units feature adjustable pitch

impellers which allows for optimum air flow and power efficiency.

There are 6 sizes in each range extending from 500 to 1000mm

diameter.

Typical Applications

Exhausting clean air and a range of toxic, noxious and

corrosive gases from a wide range of commercial

and industrial applications.

Features

O

Wide choice of speeds available.

O

Adjustable pitch impellers provide a wide range of performances.

O

Impeller blades can be GRP, aluminium, nylon or anti-static

to suit the application. GRP blades are standard.

O

Shutters are standard on the RVLE range and an optional

extra on the RDLE units. (See Special Note).

O

Can be used for free intake or ducted systems.

O

Can be mounted at angles up to 30

o

.

O

All standard motors are speed-controllable using

variable speed drives.

O

Multi-speed motors as well as motors to meet Ex d, Ex e,

Ex nA or Ex tD Standards can be supplied.

O

For applications prone to high prevailing winds refer to

Special Note.

Construction

Pressed galvanised steel base; cowls and windbands are of

plastic, fibreglass or galvanised steel.

Shutters are fitted as standard to the Beta series and are an

optional extra on the Alpha series.

Impeller blades are GRP as standard with an option of

aluminium, nylon or anti-static materials where required.

Metal components have a corrosion resistant finish.

Motors

Type - squirrel cage induction motors.

Electricity supply - motors to suit a wide range of voltages and

frequencies can be supplied.

Bearing - sealed-for life, ball.

Speed-controllable using variable speed drives.

See pages

O-3/4

for details on these motors.

Motors with 2-speed windings or to meet Ex d, Ex e, Ex nA or

Ex tD Standards can be supplied.

Internal Thermal Protection

Thermisters can be provided on all motors except where

Standards prohibit their use.

Testing

Air flow tests to BS848:Part 1, 1980

Noise tests to BS848:Part 2, 1985

Wiring Diagram

See pages

N-6/7

diagrams

DD 1, 2, 3, 9.

Special Notes

Quick select envelope curves are shown on pages

D-8/9.

Accurate

selections, including comprehensive noise data, can be obtained from your

local Fantech office or by using the Fans by Fantech Product Selection

Program. Refer to Fantech for performances at speeds other than shown.

When shutters are fitted ensure the roof unit is mounted with the shutter

spindle pointing down the roof. When shutters are fitted to the Alpha series

derate the performance by 15-20%.

Where prevailing winds are high we recommend the fitting of Magloks

®

, see

page

J-8

for details. For capacities greater than shown for the Alpha & Beta

Industrial series, refer to the HC and SS series on pages D-60/62.

SMOKE-SPILL APPLICATIONS

The Beta Industrial RSSL Series of smoke-spill fans has been fully tested

to meet the air performance and high temperature test requirements of

Standards AS/NZS1668.1:1998 and AS4429:1999.

Discharge damper fail-open latching

An additional requirement of AS/NZS1668.1:1998 with respect to

un-sprinklered buildings (300

o

C for 30mins) requires dampers to

fail-open during smoke spill operation.

The fail-open discharge damper latches come in two forms;

the first being a manual release type requiring manual closing

after the fan has been run. The second design, an electro-mechanical

type permits the shutter latch to release and close automatically

after the fan stops.

For advice on smoke-spill wiring requirements refer to

AS/NZS1668.1:1998.

See page

C-8

for details of the smoke-spill range.

TECHNICAL DATA

# Vertical discharge RVLE only.

Amperages for motors can be obtained at time of order.

HOW TO ORDER