D

ROOF MOUNTED FANS

DIMENSIONS

GL GAMMA EC SERIES

Model

CDEC…VGL

CEEC…VGL

Percentage

of full speed

(%)

*Max. Fan

Speed

r/s

Air flow

@ 0Pa

m

3

/s

Avg.

dB(A)

@ 3m kW Amps kW Amps

31

100

34

0.58

60

0.27

1.60

-

-

80

27

0.46

55

0.15

0.85

-

-

60

20

0.26

48

0.07

0.43

-

-

40

13

0.23

38

0.03

0.21

-

-

20

7

0.11

21

0.01

0.13

-

-

35

100

27

0.87

58

0.25

1.60

-

-

80

21

0.69

57

0.13

0.85

-

-

60

16

0.52

50

0.06

0.43

-

-

40

11

0.34

41

0.03

0.20

-

-

20

5

0.17

24

0.01

0.12

-

-

45

100

24

1.50

60

0.55

2.90

-

-

80

19

1.20

54

0.29

1.70

-

-

60

14

0.89

47

0.13

0.78

-

-

40

10

0.59

37

0.05

0.54

-

-

20

5

0.30

20

0.02

0.34

-

-

56

100

21

2.63

64

-

-

1.14

2.40

80

16

2.10

58

-

-

0.59

1.30

60

12

1.56

51

-

-

0.27

0.70

40

8

1.04

41

-

-

0.09

0.35

20

4

0.52

25

-

-

0.02

0.19

63

100

21

3.87

66

-

-

1.95

4.00

80

16

3.09

60

-

-

0.99

2.10

60

12

2.31

52

-

-

0.44

0.97

40

8

1.54

42

-

-

0.14

0.50

20

4

0.77

26

-

-

0.03

0.23

CEEC.. 1ph

CDEC.. 3ph

Model

CDEC…VGL

CEEC…VGL A

†

B

†

C D E

†

Approx.

weight

kg.

Approx

volume

m

3

31

310 410 50 310 520 20

0.10

35

400 500 50 420 670 23

0.22

45

620 720 50 525 900 45

0.50

56

620 720 50 525 900 49

0.50

63

710 810 50 665 1160 74

1.03

TECHNICAL DATA

Note:

If dampers are fitted, the pressure loss through them must be

added to the system resistance before selecting the fan.

BACKDRAFT DAMPER LOSSES

Dimensions

D-43

Refer to page

J-2

for more information on this product.

* The fan will maintain the set speed whether run on 50 or 60Hz supply.

The CDEC56VGL model is rated at 40

o

C for all speeds. This model cannot exceed 16.8 r/s at 60

o

C ambient.

E

C

D

A

B