D

ROOF MOUNTED FANS

D-45

GL GAMMA SERIES - BUSHFIRE CODE COMPLIANT

VA - Speed controller

Ref.

M-5

VZ - Run-on timer

Ref.

M-14

Speed controllers

Ref.

M-1

CBD - Backdraft shutter

Ref.

J-2

SD - Star/Delta switch

Ref.

M-7

ANCILLARY EQUIPMENT

DESCRIPTION

The GL Gamma Series, with bushfire code compliance,

has been developed for bushfire prone regions. They feature a

high performance backward-curved centrifugal fan and a robust

galvanised steel construction.

There are 8 sizes in the range extending from 315 to 710mm

diameter.

Typical Applications

Suitable for applications requiring the combination of

speed-controllable motors with an all metal construction.

Designed for use in commercial kitchen exhaust systems

in bushfire prone areas, see

Special Notes

.

Features

O

Quick release toggle clamps provide easy access for

cleaning and maintenance.

O

Designed for vertical discharge applications.

O

High quality bronze mesh provides ember protection.

O

Speed-controllable with electronic or auto-transformer

controllers (not on CE316VGL-BFC).

O

Compact, low profile design.

O

Choice of speeds available.

O

High performance backward-curved centrifugal fan.

O

Many 3-phase motors are 2-speed star/delta design.

O

Can be mounted at angles up to 30°.

O

Backdraft dampers are an optional extra, refer to page

J-2

for details.

O

Compliant to AS3959:2009 up to and including BAL-40.

Construction

Cowls are of galvanised steel

Ember protection - bronze mesh with maximum of 2mm aperture

Backward-curved centrifugal impellers

Powder-coating is an optional extra

Motors

Type - external rotor, squirrel cage induction motors

Electricity supply - 230V, single or 415V three-phase, 50Hz

Bearings - sealed-for-life, ball

Speed-controllable using electronic or auto-transformer speed

controllers (not CE316VGL-BFC)

Many 3-phase motors are 2-speed star/delta design.

See pages O-2/3 for details on these motors

Internal Thermal Protection

All motors are fitted with Internal Thermal Contacts as standard.

Testing

Air flow to ISO5801:1997

Noise tests to BS848:Part 2, 1985

Wiring Diagram

See page

N-8

, diagrams

ER 1, 2, 4, 5.

Special Notes

Construction of buildings in bushfire prone areas

AS3959:2009, clause 6.6.5(b) "Roof penetrations" states:

Openings in vented roof lights, roof ventilators or vent pipes

shall be fitted with ember guards made from a mesh or

perforated sheet with a maximum aperture of 2mm, made of

corrosion-resistant steel, bronze or aluminium.

Backdraft dampers

Backdraft shutters are an optional extra, refer to

page J-2

for details. The pressure loss across the shutter has to be added

to the system pressure before making fan selections.

Kitchen Hood Exhaust Systems

AS/NZS1668.1:1998, Clause 11.2.5 states that, for commercial

installations:- "kitchen exhaust fan casings and cowls shall be

manufactured from non-combustible materials that have a fusing

temperature above 1000°C".

SUGGESTED SPECIFICATION

The roof ventilators shall be of the GL Gamma Series with

bushfire code compliance as designed and manufactured by

Fantech Pty Ltd.

Impellers shall be of backward-curved centrifugal design and

driven by speed-controllable external rotor motors with integral

thermal protection.

They shall be constructed from galvanised steel and be of

vertical exhaust design.

Ember protection mesh shall be bronze or steel with

openings a maximum of 2mm. The windband shall incorporate

quick-release toggle clamps to provide easy access for cleaning

and maintenance

All data shall be based on tests on a complete assembled unit

to ISO5801:1997 for air flow and BS848:Part 2, 1985 for noise.

HOW TO ORDER