AXIAL FLOW FANS QUICK SELECTION GRAPHS

DUCT MOUNTED FANS

B

© FANTECH

2016

Pages

C-2/8

provide detailed information on these products.

An example of how to use the curves is shown on page

C-10/11

.

The dimensions for all fans are on pages

C-26/27.

Weights can be determined from details on pages

C-28/29

.

Model Numbers

O

AP - direct-driven; 315 to 2000mm diameter

O

APV - direct-driven; 315 to 2000mm diameter

O

APS - direct-driven; 315 to 2000mm diameter

O

APB - belt driven; 315 to 2000mm diameter

O

BFA - bifurcated;

400 to 1250mm diameter

q

V

- Volume Flow, m /s

3

q

V

- Volume Flow, m /s

3

p

S

F - Fan Static Pressure, Pa

p

S

F - Fan Static Pressure, Pa

0.2

0.4

0.6

1.0

2.0

4.0

6.0

10.0

20.0 30.0

1.0

2.0

4.0 6.0

10.0

20.0

40.0 60.0

0.6

0.4

0.2

200

400

600

1000

2000

3000

100

60

60

600

1000

2000

400

200

100

2 Pole

48 rev/sec

0312

0402

0502

0562

0632

0712

0802

0314

0404

0504

0564

0634 0714 0804

1004

1254

1404

System

Lines

System

Lines

65

68

70

71

78

80 78

75

90

92

92

95

71

65

94

95

91

85

56

51

64

68

87

78

69

71

90

65

52

63

68

49

49

55

64

67 71

73

73

78

88 93

dB(A) @ 3m: Inlet Side =

dB(A) @ 3m: Inlet Side =

80

80

88

91

4 Pole

24 rev/sec

73

75

69

83

92

B-52

SUGGESTED SPECIFICATION

The axial flow fans shall be of the AP/APV/APS/APB/BFA series

as designed and manufactured by Fantech Pty Ltd. and be of

the model numbers shown on the schedule/drawings.

Fan casings shall be of hot-dip galvanised steel

or pre-galvanised steel. Impellers shall be of GRP (unless nominated

otherwise), adjustable pitch and aerofoil section.

All models shall be fully tested for air flow to BS848:Part 1, 1980

or ISO5801:1997 and noise to BS848:Part 2, 1985.