AXIAL FLOW FANS GENERAL INFORMATION

AXIAL FLOW FANS PERFORMANCE DATA

C-2

© FANTECH

2016

INTRODUCTION

This section of the catalogue details the performances of a wide range of axial flow fan

types as follows:-

The above fans range in diameter from 315mm to 2000mm.

The curves shown on pages C-12 to C-24 show a range of performances for the

AP series of direct-driven axial flow fans in Type D Installation (see below). The other

fan types listed above incorporate casings or housings that impact on their

performance result. The Fans by Fantech Product Selection Program will produce

performance curves for these other fan types that have automatically taken these

losses into account.

TEST STANDARDS

The International Standards Organisation (ISO) achieved a standardised fan test code

with the publication of ISO5801:1997. This Standard replaces BS848:Part 1, 1980 upon

which it was based.

Fan performances for the Elta 1000 Series diameter have been aerodynamically tested

to BS848:Part 1, 1980 and the Elta 1400 and 2000 Series to ISO5801:1997. All three

series have been tested to BS848:Part 2, 1985 for sound performance.

The main difference between the above Standards and those they replaced, is the

installation Types A, B, C and D such that, if a fan unit is designed for use in any one of

these arrangements, the variation in performance should be established and shown.

Both BS848:Part 1, 1980 and ISO5801:1997 reflect the latest understanding of

measuring techniques and accuracy in fan performance testing.

If the same fans were tested to pre-1980 air flow and noise Standards and then to the

latest Standards, different performances would be obtained. The results from the later

Standards give differences of as much as:-

O

-5% in volume

O

-10% in pressure

O

-5% in efficiency

O

+2 to 6dB in noise

These differences should be borne in mind when making comparisons of fans tested to

the different Standards, as they are the result of the test method and not the product.

V

V

V

V

TYPE A

Free inlet

Free outlet

TYPE C

Ducted inlet

Free outlet

TYPE B

Free inlet

Ducted outlet

TYPE D

Ducted inlet

Ducted outlet

Duct Mounted Axial Fans

O

AP Series - direct driven

O

APS Series - direct driven, smoke spill

O

APB Series - belt-driven

O

BFA Series - bifurcated, direct driven

Wall Mounted Fans

O

SQ Series - square plate, direct driven

Axial Roof Units

O

RDE/RDLE Series - downflow cowl,

exhaust

O

RDS Series - downflow cowl, supply

O

RVE/RVLE Series - vertical discharge

O

RSS/RSSL Series - vertical discharge,

smoke spill

O

HC Series - high capacity, vertical

discharge

O

SS Series - smoke spill

C