AXIAL FLOW FANS GENERAL INFORMATION

AXIAL FLOW FANS PERFORMANCE DATA

C-8

© FANTECH

2016

C

SMOKE-SPILL APPLICATIONS

Smoke-spill fans have to be tested to Standard AS4429:1999 to conform with the

requirements of AS/NZS1668.1:1998. To meet the Standards Fantech conducted an

extensive series of tests covering both air flow and temperature. The air flow tests for

sizes 315mm to 1000mm diameter conformed to BS848:Part 1, 1980 and to ISO5801

for sizes 1.0m to 2.0m. The temperature tests were conducted in accordance with

AS4429:1999, although the 300°C tests were extended from 0.5 hours to 2 hours to

ensure we met the needs of some specifications.

The outcome of the series of tests is that we can supply fans ranging in diameter from

315mm to 2000mm at speeds as high as 2 pole depending on size and, for both 50

and 60Hz supply that fully comply with the Standards in all respects.

The following conditions can be met:-

Discharge damper fail-open latching

An additional requirement of the Standards relates to the function of the discharge

dampers in unsprinklered buildings. Fantech has met the requirements with two

designs, the first being a manual release type requiring manual closing after the fan

has been run. These may be used for dedicated smoke spill fans. The second design,

an electro-mechanical arrangement, permits the shutters to close automatically after

the fan stops. These are recommended for use on dual-purpose ventilation/smoke-spill

fans. Fantech has provisional patents for both designs.

For advice on Smoke-Spill wiring requirements, refer to the above Standard.

Contact our Sales Engineers for additional information.

COMPUTER SELECTION

The Fantech Product Selection Program encompasses the following features:-

O

a fan selection program

O

an attenuator selection program

O

an acoustic analysis system

O

a project schedule builder

O

enables drawings to be downloaded through dwg/dxf files and

O

enables revit models to be downloaded

O

easily updated with the latest data from our website.

To obtain a copy of our CD contact one of our Sales Offices.

O

200ºC for two hours

O

200ºC for four hours

O

250ºC for four hours

O

280ºC for 0.5 hours

O

300ºC for 0.5 hours

O

300ºC for two hours