Table of Contents Table of Contents
Previous Page  360 / 416 Next Page
Information
Show Menu
Previous Page 360 / 416 Next Page
Page Background

9

N-6

© FANTECH

2016

INSTALLATION, WIRING DIAGRAMS & FAN TROUBLE SHOOTING

WIRING DIAGRAMS - STANDARD MOTORS

N

These diagrams apply to

STANDARD

FRAME INDUCTION MOTORS

which

are used in the following products:-

Pgs

O

AD/E..D/V Alpha/Beta Series

D-4/6

Diags. DD 4, 5, 6, 7

O

AD/E..S Alpha Series Supply D-13/15

Diags. DD 4, 5, 6, 7

O

*AL..

Centrifugal fans

E-10/15

Diags. DD 1, 2, 3

O

*AP/APV.. Axial Flow fans

B-50/53

Diags. DD 1, 2, 3, 6, 7, 9

O

*APB..

Belt-driven axial fans B-50/53

Diags. DD 1, 2, 3, 6, 7, 9

O

*APS..

Belt-driven axial fans B-50/53

Diags. DD 1, 2, 3, 6, 7, 9

O

BFA..

Bifurcated fans

B-50/53

Diags. DD 1, 2, 3, 6, 7, 9

O

CGD/E..

GE Series

D-58/59

Diags. DD 1, 2, 3, 8, 9

O

*CHD/E..

Heritage Series

D-48/49

Diags. DD 1, 2, 3, 8, 9

O

*CHS..

Heritage Smoke-Spill

D-50/51

Diags. DD 1, 2, 3

O

CPD/E..

Compact 2000

A-16/18

Diags. DD 1, 4, 5, 6, 7

O

*FL..DD FlexLine Series

E-3/6

Diags. DD 1, 2, 3

O

FP..

Compact F/Proof Series A-26/27

Diag. DD 8

O

*HC..

High Capacity Series D-60/62

Diags. DD 1, 2, 3

O

JV..

JetVent Axial

F-4/5

Diags. DD 1, 2, 3

O

*MMD/E.. Multiflow Series

B-42/46

Diags. DD 1, 2, 3, 5, 6, 9

O

*PCD/E..

PowerLine Series

B-34/36

Diags. DD 1, 2, 3, 7, 9

O

*RDE..

New Generation Series D-16/19

Diags. DD 1, 2, 3, 9

O

*RDLE..

Alpha/Beta Industrial

D-7/9

Diags. DD 1, 2, 3, 9

O

*RDS..

New Generation Series D-16/19

Diags. DD 1, 2, 3, 9

O

RSS..

New Generation Series D-16/19

Diags. DD 1, 2, 3, 9

O

*RVE..

New Generation Series D-16/19

Diags. DD 1, 2, 3, 9

O

*RVLE..

Alpha/Beta Industrial

D-7/9

Diags. DD 1, 2, 3, 9

O

SCD/E...

Short Cased Series B-26/27

Diags. DD 4, 5, 6, 7

O

*SQ..

SQ Series

A-23/25

Diags. DD 1, 2, 3, 9

O

SS..

Smoke-Spill Series D-60/62

Diags. DD 1, 2, 3

W2

W2

U2

U2

V2

V2

U1

U1

V1

V1

W1

W1

L1

L1

L2

L2

L3

L3

E

E

3Ø WIRING DIAGRAMS

refer to the name plate data for correct

connection

SINGLE SPEED MOTORS

For delta ( ) wired motors

For star ( ) wired motors

Diagram DD1

Diagram DD2

Suggested wiring arrangement

U1

U1

V1

V1

W1

W1

U2

U2

V2

V2

W2

W2

L1

L1

L2

L2

L3

L3

E

E

TWO-SPEED MOTORS

with 2 separate windings (dual winding)

High speed

Red

Leads

Red

Leads

Black

Leads

Black

Leads

M

3~

Single speed only

3Ø WIRING DIAGRAMS

U1 - Red

V1 - Yellow

W1 - Blue/Black

Thermal

Contacts (TB)

White, if fitted

L1 L2 L3 N E

Codes: ..31. and ..35.

Diagram DD4

Low speed

Low speed

U1

U1

V1

V1

W1

W1

U2

U2

V2

V2

W2

W2

L1

L1

L2

L2

L3

L3

E

E

High speed

Red

Leads

Red

Leads

Black

Leads

Black

Leads

Diagram DD3

TWO-SPEED MOTORS

in Dahlander connection (tapped winding)

OVERLOAD

LO SPEED

CONTACTOR

HI SPEED

CONTACTOR

OVERLOAD

STAR POINT

CONTACTOR

BLACK

BLACK

BLACK

RED

RED

RED

SELECTOR SWITCH

OFF

HI

LO

M

3 ~

L1 L2 L3 N

BLACK

BLACK

BLACK

RED

RED

RED

OFF

HI

LO

M

3 ~

L1 L2 L3 N

Suggested wiring arrangement

SELECTOR SWITCH

HI SPEED

CONTACTOR

OVERLOAD

OVERLOAD

LO SPEED

CONTACTOR

These diagrams are current at the time of publication, check the wiring diagram supplied with the motor.

*NOTE

: Refer to the motor manufacturer’s