COMPACT 2000 SERIES

WALL, WINDOW & CEILING MOUNTED FANS

A

A-16

The Compact 2000 Series of square plate axial fans is a high

quality, robust product with 10 sizes ranging from 250 to 800mm

diameter. They are suitable for a wide range of commercial and

industrial applications and can be speed controlled to better

manage energy consumption.

Typical Applications

Capable of exhausting or supplying air in environments

containing both clean ambient air and toxic noxious gases.

See Special Note below.

Features

O

Robust high quality construction.

O

Inlet guard is incorporated as standard for models 025 to

063 and is an optional extra for models 071 and 080.

O

The 040 to 063 size range in 3 phase are fitted with

2-speed star/delta motors as standard.

O

Capable of operating across a wide temperature range;

-20

o

C to 70

o

C.

O

A flying lead with junction box and 20mm dia flexible

conduit is fitted as standard to models 025 to 063.

O

Can be mounted in any position.

O

An extensive range of matched ancillary equipment is available.

Construction

The square plate is manufactured from galvanised steel with an

additional high quality polyester epoxy finish as standard.

Impellers have GRP blades as standard; aluminium and nylon

blades are an optional extra. Non-sparking blades can be fitted

to models 071 and 080.

Motors

Type - squirrel cage induction motor.

Electricity supply - 230V single or 415V three-phase, 50Hz.

Bearings - sealed for life, ball.

Operating temperature range; -20

o

C to 70

o

C.

Maximum ambient temperature when being speed controlled is 40

o

C.

IP55 rating.

All three phase models in the 040 to 063 range are fitted with

2-speed star/delta motors as standard.

Models to 063 can be speed controlled using electronic

or auto-transformer controllers.

See pages

O-3/4

for details of these motors.

Internal Thermal Protection

Manual-reset thermal protection is supplied as standard up to

model 063 and as an optional extra on models 071 and 080.

Testing

Air flow tests to AS ISO5801:1997

Noise tests to BS848:Part 2, 1985

Wiring Diagram

See page N-6/7, diagrams DD1, 4, 5, 6, 7

Special Note

Derate the air flow by at least 25% if the air flow direction

is reversed from standard. Add the suffix “R” to fan code.

DG - Finger Guards

Ref.

J-9

The Compact 2000 Series of square plate mounted axial fans

shall be as supplied by Fantech Pty Ltd.

The axial impellers shall have GRP blades

Square plates shall be made from galvanised steel with

a polyester epoxy finish.

All models shall be fully tested to AS ISO5801:1997 for air flow

and to BS848:Part 2, 1985 for noise

SD - Star/Delta switch

Ref.

M-7

WSK - Backdraft shutter

Ref.

L-8

VZ - Run-on timer

Ref.

M-14