Don’t connect to the ‘eye’ of the base as this increases pressure

losses on the intake.

Size inlet duct to fit roof unit overflashing.

3.0 ROOF UNITS

Figure 3.1. - Roof ventilator short-circuiting of air

Ensure the roof ventilator base has an airtight seal.

If the unit does not have an airtight seal between the base and

the upstand, short-circuiting of outside air can occur thereby

reducing the amount of air being exhausted from the building.

An airtight seal between the upstand and fan base prevents

short-circuiting of outside air ensuring the fan is exhausting from

the designated space.

INSTALLATION DO’S AND DON’TS

INSTALLATION DO’S AND DON’TS