Figure 4.4. - Attenuator position relative to axial fans
Don’t site a rectangular attenuator close to an axial fan intake or
discharge. Air is accelerated through an attenuator and fan
discharge air is uneven and swirling.
Allow adequate distance between attenuators and fan.
4.0 NOISE CONTROL (Cont.)
Figure 4.3. - Attenuators in relation to bends
Don’t use attenuator splitters as shown when sited close to a
bend as the pressure loss across it will be greater than
expected.
Do ensure attenuator splitters are in the plane of the bend as
shown. Fit turning vanes only if R/W<1.0
INSTALLATION DO’S AND DON’TS
INSTALLATION DO’S AND DON’TS