INSTALLATION DO’S AND DON’TS
INSTALLATION DO’S AND DON’TS
Figure 4.2. - Volume control dampers
Don’t site volume control dampers or fittings too close to
attenuators as they can cause a dramatic increase in attenuator
pressure drop.
Allow for a settling duct between volume control dampers and
attenuators.
4.0 NOISE CONTROL
Figure 4.1. - Transitions
Abrupt transitions immediately adjacent to an attenuator will
cause the attenuator pressure drop to increase.
Ensure transitions close to attenuators are gradual or, better still,
remote.