Table of Contents Table of Contents
Previous Page  196 / 416 Next Page
Information
Show Menu
Previous Page 196 / 416 Next Page
Page Background

HERITAGE SMOKE-SPILL SERIES

ROOF MOUNTED FANS

D

© FANTECH

2016

D-50

Model

CHS...

63 125 250 500 1k 2k 4k 8k

314

35 29 21 18 10 10 8 2

316

34 26 22 18 12 12 6 0

354

28 26 22 19 10 12 11 1

356

33 25 22 19 14 8 3 0

404

28 26 21 18 11 12 12 5

406

33 28 22 19 14 10 7 3

454

27 25 20 17 11 12 12 8

456

31 30 21 18 13 11 9 5

504

26 26 21 15 12 12 12 9

506

30 29 22 16 12 10 8 6

564

26 27 23 14 13 12 12 10

566

29 29 23 15 12 10 8 7

568

30 27 22 15 15 11 11 6

In-Duct Spectrum Corrections, dB*

* Add the In-Duct Spectrum Corrections to the closest dB(A) level shown on the

fan curve to obtain the In-Duct Sound Power Level on the Inlet Side of the Unit.

CH

S

Centrifug

a

l Herit

a

ge

S

moke

S

pill

F

a

n di

a

meter in cm

F

a

n

s

peed, no. of pole

s

Motor tre

a

tment

The Heritage Smoke-Spill Series of vertical discharge centrifugal

roof units has been developed and tested for hot smoke

exhaust applications. They are constructed from durable

galvanised steel and feature a removable windband which

provides easy access for cleaning and maintenance. There are

6 sizes in the series extending from 315 to 560mm diameter.

Typical Applications

Smoke-spill exhaust systems in commercial or industrial

applications such as office buildings, shopping centres

and universities. Can also be used for dual purpose in standard

exhaust installations.

Features

O

Durable all galvanised steel construction.

O

Available in a range of speeds to suit specific applications.

O

Windband can be easily removed to allow easy access for

cleaning and maintenance.

O

To maintain reliable operation, motor is mounted out of the

airstream.

O

Can be mounted at angles up to 15°.

Smoke-Spill Standards

O

Designed to comply with the air performance and high

temperature requirement of Standards AS/NZS1668.1:1998

and AS4429:1999. Both Standards are mandatory for

smoke-spill installations.

O

Tests up to 300°C for 2 hours have been successfully

concluded.

O

Backdraft dampers are not fitted to these units so fail-open

latching devices are not required.

Construction

Cowls are of galvanised steel. Impellers are backward-curved

centrifugal design.

Motors

Type - Standard TEFC squirrel cage induction motors

Electricity supply - 415V, three-phase, 50Hz

Bearings - sealed-for-life, ball

Multi-speed motors can be supplied

Motors are selected to suit the nominated smoke-spill

temperature requirements as prescribed in AS/NZS1668.1:1998

See pages

O-3/4

and

C-8

for details on these motors

The roof ventilators shall be of the Heritage Smoke-Spill Series

vertical discharge type as designed and manufactured by

Fantech Pty Ltd.

The cowl shall be of galvanised steel. Impellers shall be

backward-curved centrifugal design and driven by motors

selected to suit the elevated temperatures of the nominated

smoke-spill application.

All performance data shall be based on tests on a complete

assembled unit to ISO5801:2007 for air flow and ISO3744: 2010.

Smoke-spill tests shall be to AS/NZS1668.1:1998 and

AS4429:1999.

DESCRIPTON

NOISE DATA

HOW TO ORDER

SUGGESTED SPECIFICATION

Internal Thermal Protection

Thermisters can be fitted on request. If fitted they must not

operate under smoke-spill mode.

Testing

Air flow tests to ISO5801:2007

Noise tests to ISO3744:2010

Wiring Diagram

See page

N-6

, diagrams

DD 1, 2, 3.